- A hot surface igniter only starts the fire. It cannot hold a flame, so burners that light and then die a few seconds later almost always point at flame sensing or grounding, not the igniter.
- A furnace with a hot surface igniter has no standing pilot at all. If you are looking for a pilot light to relight and there is no pilot assembly, your furnace proves flame electronically instead.
- The single most useful thing a homeowner can do is watch one full cycle through the sight glass and note exactly where it stops: no glow, glow with no flame, or flame that quits.
- Silicon carbide igniters are brittle and fail from vibration, moisture and finger oils as often as from age. Repeated failures usually mean something else in the system is stressing the part.
- Filters, thermostat settings, breakers, a properly seated door panel and clear vent terminations are all fair game for a homeowner. Anything inside the burner compartment or on the gas train is licensed work in BC.
- Never keep resetting a furnace that locks out repeatedly. Repeated trials dump unburned gas into the heat exchanger and the vent.
If your gas furnace fires and then shuts down a few seconds later, the hot surface igniter is probably not the part that failed. The igniter has exactly one job: glow hot enough to ignite gas at the burners, then step out of the way. Once flame is established the control board stops powering it entirely. So a burner that lights cleanly and then dies is a flame-proving problem, not an ignition problem, and swapping the igniter will not fix it. A dead igniter looks completely different from the outside: the inducer motor runs, the board waits, no orange glow appears in the sight glass, no gas is ever released, and the furnace locks out without ever making a flame. Telling those two failures apart takes about three minutes of watching one cycle, and it is the difference between a small parts job and a wasted afternoon.
Can a bad hot surface igniter make my burners go out?
Not once the burners are lit. The igniter is energised only during the trial-for-ignition window at the start of a heat cycle. The control board powers the element, waits for it to reach temperature, opens the gas valve, and then cuts power to the igniter as soon as flame is proven. From that point the igniter is a cold piece of ceramic sitting in the burner box. It has no ability to shut the gas off.
This matters because the two most common complaints in this category get lumped together online. “My furnace will not light” and “my furnace lights and then quits” are different faults with different parts behind them. The first can genuinely be the igniter. The second is nearly always the flame sensor, the ground path, or a safety switch opening after the burners are already running.
There is one edge case worth knowing. On some designs the igniter and the flame sensing rod are combined into a single element that ignites first and then senses flame. If your furnace uses that arrangement, a degraded element can in fact cause a drop-out after a few seconds. It is uncommon in residential equipment around the Lower Mainland, but a technician confirms which arrangement you have by looking at the burner assembly and the wiring, not by guessing from the symptom.
Which ignition system does my furnace actually have?
Three systems show up in Metro Vancouver basements and crawl spaces, and the troubleshooting path splits immediately depending on which one is in front of you.
A standing pilot burns continuously. There is a small pilot hood, a thermocouple or thermopile clipped beside it, and a gas valve with a knob marked for pilot, on and off. Lighting instructions are printed on a label attached to the appliance. If that pilot will not stay lit after you release the knob, the fault is usually a weak or dirty thermocouple, a partially blocked pilot orifice, or a draught blowing across the pilot. These furnaces are getting old now, and many in older Vancouver and Burnaby houses are well past the point where parts are easy to source.
Intermittent spark ignition lights a small pilot on demand with an audible tick, proves it, then opens the main valve. You will hear rapid clicking at the start of the cycle.
Hot surface ignition has no pilot whatsoever. A ceramic element glows orange, gas is released directly at the burners, and a separate metal rod sitting in the flame confirms the fire is there. If you have been searching for a pilot light on a furnace like this and cannot find one, that is why. There is nothing to relight.
- Silicon carbide igniters look like a flat, forked or ladder-shaped grey element in a ceramic block. They are extremely brittle and break from a bumped panel or a dropped screwdriver.
- Silicon nitride igniters look like a slim rod or pin, are far more rugged, and generally warm up faster. Many are driven at a reduced voltage rather than full line voltage.
- The two are not interchangeable. Fitting the wrong style, or the wrong voltage class, either cooks the element quickly or never gets it hot enough to light gas reliably.
- Never touch the glowing portion of any igniter with bare fingers. Residue from skin leaves a hot spot on the element that cracks it within the next few cycles.
What happens between the thermostat calling and the burners lighting?
A furnace runs the same ordered sequence every single cycle, and every safety in the chain has to close before the next step is allowed. Watching where the sequence stops tells you more than any parts list. Stand where you can see the sight glass, set the thermostat well above room temperature, and watch one complete attempt from silence to warm air.
| Stage | What you can see or hear | What a fault at this stage looks like |
|---|---|---|
| Thermostat calls for heat | A low voltage signal reaches the control board; nothing moves yet | Nothing at all happens, no board light, no hum: check power, the door panel switch and the thermostat first |
| Inducer motor starts | A small motor spins up before anything else, usually with a rising whine | Inducer hums without spinning, or spins and immediately stops |
| Pressure switch proves draught | A faint click at a round switch with a rubber hose running to it | The board quits before the igniter ever glows: blocked vent or intake, cracked hose, water sitting in the condensate trap |
| Igniter warms up | A steady orange glow visible through the sight glass for several seconds | No glow at all, or a glow that appears and then the sequence stops before gas is released |
| Gas valve opens and burners light | A soft whoosh and a row of blue flames travelling across the burners | A good bright glow with no flame following it points at the gas valve, the valve wiring or gas supply, not the igniter |
| Flame is proven | The glow fades out while the burners keep running | Burners run a few seconds and cut out, then the whole sequence repeats: this is flame sensing or grounding |
| Blower starts | Warm air at the registers after a short built-in delay | Burners run for several minutes then drop out while the fan keeps going: a limit is tripping on restricted airflow |
Why do the burners light and then die after a few seconds?
Because the furnace cannot confirm the flame is really there. Flame proving works on a principle called rectification. A small metal rod sits directly in one of the burner flames while the control board applies a voltage to it. Burning gas conducts electricity in one direction only, so the board reads back a very small direct current, measured in microamps. That tiny current is the furnace’s only proof that gas is actually burning rather than pouring into the heat exchanger unlit. If the signal is too weak, the board closes the gas valve within a couple of seconds and either retries or locks out.
The signal weakens for reasons that have nothing to do with the igniter. A whitish oxide film builds on the sensing rod over years of service and insulates it. The rod can drift out of the flame envelope after a burner assembly has been removed and refitted. Cracked porcelain at the base of the rod bleeds current to the cabinet. Most importantly, rectification needs a solid electrical ground back through the burner assembly and the furnace chassis, so a corroded ground screw, a loose burner rack or a poorly grounded receptacle will produce exactly the same symptom as a filthy sensor.
There is a second family of causes that mimics this and gets misdiagnosed constantly. If the flame itself is unstable, the sensor is telling the truth. Burners starved of combustion air, a partially blocked flue, a cracked heat exchanger disturbing the flame pattern, or a rollout condition will all cause a genuine loss of flame. This is the case where the obvious answer is wrong, and it is why cleaning a flame sensor is a diagnostic step and not a repair. If a cleaned sensor buys you three days and the fault returns, stop chasing the sensor and have the combustion side inspected properly.
Reading the diagnostic flash code helps here, and it is something you can do safely. Most furnaces blink a pattern through the sight glass or a small window in the panel. Count the flashes and the pauses, then read the pattern against the legend printed on the inside of the furnace door, not against a chart found on some other manufacturer’s site. The same flash count means different things on different equipment.
What should I check first, and what does each check rule out?
Work outside in. Every item below is something a homeowner in British Columbia may legally and safely do without opening the burner compartment, and each one either eliminates a whole branch of the fault tree or points straight at it.
- Thermostat: set to heat, set temperature well above the room, fresh batteries if it takes them. A thermostat that has quietly reverted to a schedule or lost its batteries produces a furnace that appears dead.
- Breaker and the service switch: check the panel, and check the wall switch beside the furnace that looks like a light switch. That switch gets flipped by accident more often than anything else in the mechanical room.
- Door panel: the burner compartment door has an interlock switch that must be pressed by the panel. If the panel is not fully seated on its clips the furnace will not run at all.
- Filter: pull it and hold it up to a light. A loaded filter starves airflow, overheats the heat exchanger and trips the high limit, which looks like a furnace that lights fine then quits after several minutes.
- Registers and returns: open supply registers, and make sure nothing is stacked against the return grille. Same failure mode as a plugged filter.
- Vent and intake terminations outside: look for leaves, wasp or mason bee nests, spider webs across the intake screen, or shrubs grown across the pipes. A blocked termination stops the pressure switch from closing, so the igniter never glows.
- Condensate: on a high efficiency furnace, look for water pooling under the cabinet or a trap that is visibly full and not draining. A blocked condensate path backs water into the inducer housing and opens the pressure switch.
- Other gas appliances: if your gas water heater and range are working normally, gas supply to the house is present and the problem is inside the furnace.
- Flash code: record the blink pattern before you cut power. Resetting the breaker erases it.
| What you observe | Most likely area | What this observation rules out |
|---|---|---|
| Nothing at all: no fan, no glow, no board light | Power supply, service switch, door interlock, board fuse, thermostat | Rules out the igniter, the gas valve and flame sensing entirely |
| Inducer runs, then everything stops before any glow | Pressure switch, vent or intake blockage, cracked hose, condensate backup | Rules out the igniter and the flame sensor |
| No glow appears but the sequence otherwise runs on time | Igniter element, its harness, or the board output that drives it | Rules out the flame sensor and, usually, the gas valve |
| Strong even glow, no flame follows, board retries and locks out | Gas valve, valve wiring, manual shutoff, gas supply to the appliance | Rules out the igniter, which clearly did its job |
| Burners light, run a few seconds, cut out, cycle repeats | Flame sensing, ground path, or unstable flame from a combustion fault | Rules out the igniter |
| Burners run several minutes, cut out, blower keeps running | High limit tripping from restricted airflow or a failing blower | Rules out ignition and flame proving completely |
| Glow is dull, patchy, or the element is visibly cracked | The igniter itself, plus whatever stressed it | Confirms the igniter but does not excuse skipping the flame path check |
Why did the igniter fail in the first place?
A furnace that eats igniters has an underlying problem, and replacing the element on a schedule is not a repair. The element is designed for a set number of heating cycles at a controlled voltage. Anything that increases either the number of cycles or the electrical stress shortens its life sharply.
Short cycling is the biggest offender. An oversized furnace in a smaller house, a thermostat mounted in a draught or above a heat source, or a restricted duct system will all drive far more starts per day than the equipment was designed around. Every start is one more thermal shock to a brittle ceramic part.
Supply voltage matters too. A silicon carbide element run at the high end of its voltage range will glow beautifully and die early. Some control boards regulate the igniter output and some do not, which is one reason a generic replacement of the wrong class fails prematurely even though it fits the bracket.
Then there is handling. These parts break from vibration, from a service panel being slammed, and from bare fingers during a previous repair. In a damp crawl space, corrosion at the igniter plug and along the harness raises resistance and produces intermittent failures that come and go with the weather. If the same part has now failed twice in a couple of seasons, ask the technician to check cycle rate, static pressure across the furnace and the igniter supply, not just to fit another element.
What is different about furnaces in Metro Vancouver homes?
Our climate produces a specific set of ignition faults. Winters here are long, mild and wet rather than sharply cold, so furnaces run many short cycles across a lot of days instead of long steady burns. That cycle count is hard on igniters, and it is why a furnace here can wear out an element on a timeline that surprises people who moved from a drier, colder part of the country.
Location makes it worse. A large share of furnaces around Burnaby, New Westminster, the North Shore and East Vancouver sit in vented crawl spaces, unheated garages or half-finished basements. Persistent damp corrodes flame sensor rods, ground screws, igniter terminals and pressure switch hoses. A furnace that misbehaves through a stretch of rain and then behaves in a dry week is telling you something about connections and moisture, not about the burners.
Side wall vent terminations on high efficiency furnaces are the other regional pattern. Wind driven rain, moss, leaf litter and nesting insects all find their way into an intake screen mounted a couple of feet off the ground. A partially blocked intake stops the pressure switch from proving, so the igniter never gets its turn and the furnace looks like an ignition failure when it is really a venting one.
Older housing stock adds its own wrinkle. Post war Vancouver homes often have undersized returns and duct runs that were never rebalanced after a furnace change, which raises static pressure and trips limits. In stratas, the mechanical room may be shared or the furnace may be in a closet with dedicated combustion air arrangements, and work there normally needs building manager notice as well as a permit.
Finally, the regulatory side. Gas work in British Columbia is regulated by Technical Safety BC. Servicing, altering or replacing gas appliances and gas piping requires a licensed gas fitter, and appliance replacement requires a permit. That is not paperwork for its own sake. It is the reason a furnace that has been worked on by an unlicensed hand is worth having properly inspected before another winter.
When do I need a licensed gas technician?
The homeowner boundary is clear in BC. You may operate the appliance, set the thermostat, change filters, restore power, seat the door panel, keep vent terminations clear, look at the condensate for standing water, and read the flash code. Everything past the burner compartment door is licensed gas work.
Specifically, do not remove the burner assembly, do not sand or scrub a flame sensor, do not replace an igniter, do not adjust or bypass a gas valve, and never jump out a pressure switch, limit or rollout switch to get heat. Those switches are the reason unburned gas does not accumulate in your heat exchanger. Bypassing one converts an inconvenience into a hazard.
Call right away if you smell gas at any point, if the burner flame is yellow and lazy rather than blue, if you see scorching or discoloured metal around the burner opening, if a carbon monoxide alarm sounds, or if the furnace has locked out repeatedly and you have been resetting it. Each failed trial releases gas before shutting down, and repeated attempts are not harmless.
BC Wide Home Services Ltd has served Metro Vancouver from Burnaby since 1999 as an independent Technical Safety BC licensed contractor, licences LGA0090068 and CGA0028029. We are not a factory authorised dealer for any manufacturer; we are a licensed contractor that services the gas furnaces already in Lower Mainland homes. If your burners will not stay lit and the checks above have not sorted it, call (604) 473-9690 and ask for a diagnostic on the ignition sequence, and request a written quote before any parts work goes ahead.
Frequently asked questions
My furnace has no pilot light to relight. Is it broken?
No. Furnaces with hot surface ignition do not have a standing pilot at all. A ceramic element glows orange, the gas valve opens directly at the main burners, and a separate sensing rod confirms the flame electronically. There is nothing to relight, and no lighting knob to turn, so a missing pilot is normal rather than a fault.
The igniter glows brightly but the furnace still will not light. What does that mean?
It means the igniter is doing its job and the problem is downstream of it. Gas is not reaching the burners, which points to the gas valve, the wiring to the valve, the manual shutoff, or supply to the appliance. Check whether your gas water heater and range still work to confirm the house has gas, then have a licensed technician test the valve, because gas train work is not a homeowner task in BC.
Can I clean the flame sensor myself to stop the burners cutting out?
In British Columbia, no. Reaching the sensor means opening the burner compartment on a gas appliance, which is licensed gas fitter work. It also matters that cleaning a sensor is a diagnostic step, not a repair: if the fault returns within days, the real cause is usually a ground path problem or an unstable flame from a combustion or venting issue that needs to be found properly.
How long should a hot surface igniter last?
Life is measured in heating cycles rather than years, so it varies enormously with how the system runs. Brittle silicon carbide elements in a short cycling, damp crawl space installation wear out far faster than a rod style element in a well matched system. If you are replacing igniters repeatedly, the useful question is what is driving the cycle count or the electrical stress, not which brand of element to buy next.
Is it safe to keep resetting the furnace at the breaker to get heat overnight?
It is not. Every ignition attempt releases gas before the control shuts the valve, and repeated forced trials put unburned gas into the heat exchanger and vent. One reset to clear a one-time lockout is reasonable. A furnace that locks out again should be left off at the service switch until a licensed technician has looked at it.
The furnace runs for several minutes and then the burners quit while the fan keeps blowing. Is that the igniter?
No, that timing rules the igniter out entirely, because the igniter is de-energised the moment flame is proven. Burners dropping out after several minutes while the blower continues is the classic signature of a high limit tripping on restricted airflow. Start with the filter, the supply registers and the return grille, and if it persists, the duct system or blower needs to be assessed.
Does a damp crawl space really cause ignition faults?
Yes, and it is common around Metro Vancouver. Sustained damp corrodes flame sensor rods, ground screws, igniter terminals and pressure switch hose fittings, all of which produce intermittent lockouts. A telltale sign is a furnace that misbehaves during a long wet stretch and settles down in dry weather. Mention that pattern when you call, because it changes what a technician checks first.
BC Wide Home Services — Lower Mainland home-comfort specialists since 1999
Technical Safety BC Licensed Gas Contractor (LGA0090068) · Class B Gas Licence (CGA0028029) · Red Seal technicians · Evening and weekend calls · Diagnostic service calls $189.00 · Free in-home estimates on replacements (the $189.00 is waived if you replace with us). Call 604-473-9690 or book a free replacement estimate.
Frequently asked questions
How often should a furnace be serviced?
How long does a furnace last in Vancouver's climate?
Why is my furnace blowing cold air?
How much does a new furnace cost in Vancouver?
What is the most reliable furnace brand?
What HVAC services does BC Wide offer in Metro Vancouver?
How long has BC Wide been in business?
What areas do you serve?
What Greater Vancouver homeowners say about BC Wide
Get a Free Quote — Right From This Page
Request a Free Quote
Get Comfortable — Talk to BC Wide Today
Free, no-obligation quotes. TSBC-licensed local technicians serving Greater Vancouver since 1999.