★ 4.7 Google rating · Serving Greater Vancouver since 1999
ServicesBrandsRebates ReviewsAboutContact 📞 Call (604) 473-9690

Lochinvar Boiler Code E01 — Memory Lockout | BC Wide

Boilers, Error Codes, Hvac

Lochinvar Boiler Code E01 — Memory Lockout | BC Wide — BC Wide Heating & Air Conditioning, Greater Vancouver
Home › Lochinvar Boiler Code E01 — Memory Lockout | BC Wide

Lochinvar Boiler Code E01 — Memory Lockout | BC Wide

Quick answer

Lochinvar boiler error code E01 is a memory lockout: the control logged a lockout at the same moment the power dropped, or it detected a fault in its own memory, and its parameter settings may be corrupted. Confirm that meaning against the manual for your unit. Expect no heat and, if the boiler also heats an indirect tank, fading hot water. Confirm power is stable, reset once only if the manual allows it, and if E01 returns, book a licensed gas technician at (604) 473-9690.

If your Lochinvar boiler is showing E01 (Memory Lockout), here’s exactly what it means and what to do. This guide is part of our full Lochinvar boiler error code list.

Severity: Critical — likely no heat / lockout.

What E01 means on a Lochinvar boiler

A lockout has occurred at the same time as a power outage, or the control detected a memory fault. The control parameter settings may be corrupted.

Common causes

  • Power outage during a lockout
  • Corrupted control parameter settings
  • Control module memory fault

What you can safely check first

  1. Confirm building power is stable
  2. Reset once using the RESET button on the display
  3. If it persists, call a technician — the control module typically needs to be reprogrammed or replaced

Only attempt the basics above. Do not open the gas train, burner compartment or control wiring.

When to call a technician

This is a fault that should be diagnosed by a licensed technician. Repeated lockouts on a Lochinvar boiler usually point to a real fault that will keep recurring until it’s fixed properly — and continually resetting power can hide a safety issue.

BC Wide Heating & Air Conditioning has serviced Greater Vancouver boilers since 1999. Diagnostics and repairs are carried out by our own Technical Safety BC–licensed technicians (gas contractor licence LGA0090068, Class B Gas Licence CGA0028029) — never subcontractors — and we’re rated 4.7★ across 180+ Google reviews. Honest pricing and free written quotes on replacements.

Lochinvar boiler repair across Greater Vancouver

If a Lochinvar boiler showing E01 won’t reset or has locked out, don’t keep cycling the power — you can mask a real fault or a safety condition. BC Wide provides fast boiler repair and emergency HVAC service 7 days a week throughout the Lower Mainland. Call 604-473-9690 or email info@bcwide.ca and a licensed technician will diagnose the real cause and get your heat & comfort back. See our emergency HVAC service.

Related Lochinvar boiler codes

Frequently asked questions

Is E01 on a Lochinvar boiler serious?

It’s a lockout/safety code — the boiler has shut down and needs prompt diagnosis. BC Wide repairs Lochinvar boilers 7 days a week across Greater Vancouver.

How do I reset a Lochinvar boiler after E01?

You can try one power cycle at the breaker/switch after checking the filter and thermostat. If the code returns, stop resetting it and book a licensed technician — a recurring code is a real fault, not a glitch.

Lochinvar Boiler Error Code E01: what it means for your heat, hot water and safety

In plain terms, E01 tells you the boiler’s control has stopped trusting its own memory. Keep the explanation at the top of this page in mind: a lockout happened at the same time as a power outage, or the control found a memory fault, and the parameter settings it relies on may no longer be correct. Confirm that wording against the manual for your unit, because control generations differ. What matters to you as the owner is what happens next: the boiler will not fire, and it stays that way until the condition is cleared and the control’s settings are known to be sound.

For heat, that means radiators, in-floor loops or fan coils served by the boiler slowly cool down. A hydronic system holds a lot of warm water, so the house can feel normal for an hour or two and then fall off, which is why many owners first notice E01 the next morning rather than the moment it happened.

For hot water, it depends on how your system is piped. If the boiler also heats an indirect storage tank, the stored water will run lukewarm and then cold once the tank is drawn down. If your home has a separate gas tank water heater, your hot water is not affected by this code at all, and that is a useful clue when you describe the problem to us.

For safety, the lockout itself is the boiler doing its job: it refuses to run rather than run on settings it cannot vouch for. The concern is not the screen, it is what may sit underneath it. A memory lockout can be stacked on top of an earlier lockout that had its own cause, such as an ignition or flame problem, and a power cut in the middle of that lockout scrambles the clean record of what went wrong first. That is why resetting over and over is the wrong answer.

These are the symptoms owners most often describe to us when they call about this code:

  • The display shows E01 and the boiler will not start a heating cycle.
  • Radiators or heated floors are cooling even though the thermostat is calling for heat.
  • Hot water from an indirect tank is turning lukewarm, then cold.
  • The code appeared right after a power flicker, a storm outage or a tripped breaker.
  • The boiler seems to have forgotten settings, or schedules and temperatures look different from before.
  • A reset clears the screen briefly, then E01 or another lockout comes back.
  • The circulator pump is silent and the venting is quiet at times it would normally be running.

Lochinvar boiler error code E01: likely causes and the checks you can safely do

Here are the likely causes in the order we most often find them, with the checks a homeowner may safely do and the point where each becomes a job for a licensed gas technician. The owner checks are deliberately limited. Gas work and most electrical work on a boiler are restricted to licensed trades in BC, and nothing in this list involves opening the boiler cabinet.

One reset, not five. If the manual for your unit allows a reset from the display, do it once, and only after building power is back and stable. If the boiler fires and runs a normal heating cycle, keep an eye on it and still mention the event when you next book service, because a memory lockout is worth logging. If E01 comes back, stop. Repeated resets can mask the original fault, and repeated ignition attempts on an unresolved problem are exactly what the lockout exists to prevent.

Do not open the boiler cabinet, remove the burner cover, touch the gas valve or control wiring, or jumper or bypass any switch or sensor. Do not power-cycle the boiler again and again to clear the display, and do not try to re-enter installer settings from a menu you are not familiar with. Write down exactly what the screen shows, and take a photo if you can; that saves diagnostic time on the visit.

Gas and carbon-monoxide safety: if you smell gas (a rotten-egg or sulphur odour) or a carbon-monoxide alarm sounds, do not reset the boiler, do not operate light switches, and do not use your phone inside. Get everyone out of the house, then call FortisBC or 911 from outside. Once responders have cleared the home, call us at (604) 473-9690. Every home with gas appliances should have working CO alarms near the sleeping areas and on each level.

Likely cause (most common first)What you can safely checkWhen it becomes a licensed call
1. A power outage or flicker that hit while the boiler was already in a lockoutConfirm building power is back and stable, the boiler service switch is on, and the breaker has not tripped again. Reset once only if your owner manual allows it.E01 returns after one reset, the breaker trips again, or you do not know why the boiler was locked out before the power dropped.
2. An earlier lockout hiding underneath, such as an ignition or flame problemConfirm the manual gas valve to the boiler is open (on a typical quarter-turn valve the handle sits in line with the pipe), the thermostat is calling for heat, and the outdoor intake and exhaust terminals are clear of leaves, snow or nests.Any sign the burner tried and failed to light, any gas smell, or any lockout that comes back after a reset.
3. Corrupted control parameter settingsNote whether schedules, temperatures or other settings on the display look different from what you are used to, and write down exactly what the screen shows.Always. Re-entering installer-level parameters needs the correct values for your boiler, venting and system, and wrong values can affect safe operation.
4. Control module memory faultCheck that the visible condensate drain line is not kinked, disconnected or backed up, so a second problem is not confusing the picture.Always. Reprogramming or replacing the control module is licensed work and must be followed by full safety testing.
5. Unstable or interrupted power reaching the boilerNote whether lights flicker or other equipment resets at the same time, and whether outages are frequent in your area.When power problems keep recurring at the boiler, the supply circuit needs checking by a licensed technician or electrician.

How our Lochinvar E01 repair visit works, step by step

This is what a correct E01 visit looks like from the installer’s side of the boiler, and what you should expect to receive in writing at the end of it.

The parts most often involved with a memory lockout, in general terms, are the control module itself, the display or user interface, and the wiring and connections that carry power and signals between them. Where the original lockout had its own cause, we commonly find ignition components, flame sensing, condensate handling or venting involved. A control module is one of the more expensive parts on a modern condensing boiler, which is exactly why we confirm it has actually failed before recommending it, rather than swapping it just to make a code go away.

What you should see in writing: the code and what the control recorded, the readings that matter (supply power, gas pressure, combustion results), the cause we found, what we did, any parts replaced, and anything we recommend but did not do. Keep that record with your boiler paperwork; the next technician who works on the unit will thank you for it.

  • 1. Booking and triage by phone. We ask what the display shows, when it started, whether there was an outage, whether you still have heat or hot water, and whether anyone has smelled gas or heard a CO alarm. If there is a gas smell, we direct you to leave and call FortisBC or 911 first. We offer same-day where we can, but we never promise an arrival window we cannot guarantee; in a cold snap, no-heat calls in homes with infants, seniors or medically vulnerable people are triaged first.
  • 2. Look before touching. The technician reads the display, records whatever lockout history the control still holds, and checks the surroundings: venting and terminals, condensate line and trap, gas piping, the circulator, and the near-boiler piping and pressure.
  • 3. Power checks with the right meters. Using a multimeter, we verify supply voltage, polarity and grounding at the boiler and confirm the circuit is stable. A memory lockout driven by poor power will come back no matter what else is fixed.
  • 4. Find the first fault. Because E01 can sit on top of an earlier lockout, we work out what the boiler was locked out for before the power dropped. That usually means checking ignition and flame sensing, measuring gas pressure with a manometer, and testing combustion with a calibrated combustion analyser once the boiler can fire.
  • 5. Restore or replace the control. If the parameter settings are corrupted, they are re-entered to match your boiler, venting and system as documented by the manufacturer. If the control module itself has failed, it is replaced with the correct part for your model.
  • 6. Test every safety. We confirm the boiler’s safety controls, such as the high-limit, water-pressure or low-water protection, flame safeguard and venting safeties, respond as designed, and that the boiler runs cleanly through several calls for heat and, if fitted, an indirect tank call.
  • 7. Written quote before work beyond diagnosis. Diagnosis comes first. If the fix goes beyond it, you get a written quote describing the work and parts before anything is done, and nothing is replaced without your approval.

Repair or replace an older Lochinvar boiler that keeps showing E01?

One E01 after a storm outage on a boiler that is otherwise healthy is a repair call, not a replacement conversation. A control that reprograms cleanly, or a replacement module that passes every safety test, can give many more years of service. The calculation changes when E01 is one of several problems on an older unit.

We look at the whole boiler, not just the code. The heat exchanger matters most on a condensing boiler. Metro Vancouver water is soft, so hydronic trouble here is usually sludge, magnetite and corrosion rather than limescale, and a fouled or corroding heat exchanger on an older unit changes whether a control replacement is money well spent. We also weigh parts availability for older control generations, how often the boiler has needed service over recent heating seasons, whether the venting and condensate handling meet current requirements, and whether the boiler is sized correctly for the house.

If replacement is on the table, we put both options in writing so you can compare them side by side: the repair, with what it fixes and what it leaves, and the replacement, with the scope of work, the gas permit and the inspection it involves. You decide; we do not pressure a replacement over a sound repair.

Leans toward repairLeans toward replacement
A single E01 after a known power outageE01 returning alongside other lockouts on an older unit
Heat exchanger clean and in good conditionHeat exchanger fouled, corroded or leaking
Control parts readily available for your modelControl parts discontinued or hard to source
Good service history and clean combustion readingsRepeated repairs over recent heating seasons
Venting, condensate and piping in good orderVenting or piping needs significant correction regardless

Lochinvar boiler error code E01 service in Vancouver, Burnaby, Surrey and across Greater Vancouver

We are based in Burnaby and service Lochinvar boilers across Metro Vancouver, including Vancouver, Burnaby, Surrey, Richmond, Coquitlam, the Tri-Cities (Coquitlam, Port Coquitlam and Port Moody), the North Shore (North Vancouver and West Vancouver), New Westminster, Delta and Langley.

The housing stock shapes what an E01 call looks like. In many older Vancouver, Burnaby and New Westminster homes, the boiler sits in a basement that has been renovated around it, sometimes on electrical circuits that were extended over the years, so we pay close attention to how power actually reaches the boiler. Many homes in Richmond, Surrey, Delta and Langley are newer, and condensing boilers there often vent through a side wall where terminals can end up close to fences, shrubs and landscaping. Hillside homes on the North Shore and in the Tri-Cities can see heavier wind-driven rain and, at higher elevations, the occasional snowfall that can bury a low terminal. In strata townhomes and buildings, mechanical spaces and vent runs are often tight or shared, and work may need notice to the strata.

Our wet coastal climate matters for this code in two ways. Winter windstorms and heavy rain bring power interruptions, which are the most common trigger for a memory lockout. And when an outage hits on a cold night, boilers across a whole neighbourhood can lock out at once, so service demand spikes the next morning. We offer same-day where we can and triage no-heat calls by need, and we will tell you honestly if we cannot reach you that day.

If outages are frequent where you live, ask us on the visit about protecting the boiler’s supply. Whether that makes sense depends on your home’s electrical setup and is assessed on site, never guessed over the phone.

Why Greater Vancouver homeowners call BC Wide for a Lochinvar E01 lockout

BC Wide Home Services Ltd is an independent, Technical Safety BC licensed gas contractor (gas contractor licence LGA0090068, Class B gas licence CGA0028029), serving Metro Vancouver since 1999. We are not a factory-authorized dealer or warranty centre for Lochinvar or any other manufacturer; we are the independent contractor who services the boiler you already own. If your boiler is still under a manufacturer warranty, check your warranty paperwork before work begins, because some claims have to go through specific channels.

Call (604) 473-9690 with what your display shows and when it started, and we will tell you plainly whether it sounds like a single reset and watch, or a visit.

  • Licensed gas fitters do the gas work: our own technicians, not subcontractors.
  • Permits and inspections are taken out where BC rules require them, including boiler replacement and gas piping changes.
  • A written quote before any work beyond diagnosis, with no parts added without your approval.
  • Measured results: combustion, gas pressure and safety tests are recorded, not guessed.
  • Honest timing: same-day where we can, never a guaranteed arrival window.
  • Boiler brands we service include Lochinvar, Navien, IBC, Viessmann, Weil-McLain, Bosch and Rinnai.

More questions homeowners ask

What does E01 mean on a Lochinvar boiler?

E01 is a memory lockout: the control recorded a lockout at the same time as a power outage, or it detected a memory fault, and its parameter settings may be corrupted. Confirm the exact wording against the manual for your unit. In practice, the boiler will not fire until the condition is cleared and the settings are verified.

Can I reset a Lochinvar boiler showing E01?

Once, if your owner manual allows it and building power is back and stable. Use the reset described in the manual and watch whether the boiler runs a normal heating cycle. If E01 comes back, stop resetting and call a licensed gas technician, because repeated resets can hide the fault behind the original lockout.

Is it safe to run my Lochinvar boiler after an E01 code?

If a single reset clears it and the boiler runs normally, it is generally reasonable to use it while you book a check, but the cause still needs confirming. If the code returns, leave the boiler off until a licensed technician has tested it. If you smell gas or a CO alarm sounds, leave the house and call FortisBC or 911 from outside.

Why did my Lochinvar boiler show E01 after a power outage?

Because the outage arrived while the boiler was in a lockout, or it disturbed the control’s memory. Storm-season outages in Metro Vancouver are a common trigger. The key question a technician answers is whether the boiler was already locked out for another reason before the power dropped.

Does Lochinvar error code E01 mean I need a new control board?

Not necessarily. Sometimes the parameters only need to be re-entered correctly and verified, and sometimes the control module has genuinely failed and must be replaced. We confirm which with testing before recommending a part, and you receive a written quote before that work.

Who fixes Lochinvar boiler error code E01 near me in Greater Vancouver?

BC Wide is an independent TSBC-licensed gas contractor in Burnaby that services Lochinvar boilers across Vancouver, Burnaby, Surrey, Richmond, Coquitlam, the Tri-Cities, the North Shore, New Westminster, Delta and Langley. Call (604) 473-9690; we offer same-day where we can and quote in writing before any work beyond diagnosis.

4.7★181+ Google reviews
27+Years serving Greater Vancouver
20+Brands serviced
$0Free written estimates on installs

Frequently asked questions

How often should a boiler be serviced?
Annual servicing is recommended for all residential boilers. BC Wide's annual service includes combustion analysis, heat exchanger inspection, expansion tank pressure check, condensate trap cleaning, and a full safety check. Annual maintenance is also required to keep most manufacturer warranties valid.
How much does a new boiler cost in Vancouver?
A typical residential high-efficiency gas boiler in Metro Vancouver costs $7,500–$15,000 installed, depending on size, brand, and whether the system is heating only or a combi unit that also handles hot water. BC Wide provides a free written quote with three options at different price points.
How long does a boiler last?
A well-maintained cast-iron boiler can last 25–30 years, a modern high-efficiency condensing boiler typically lasts 15–20 years, and a combi boiler 12–18 years. Annual servicing has the single biggest impact on lifespan.
My boiler is making a banging or kettling noise. Is that dangerous?
Kettling (a banging or whistling sound) is usually caused by limescale build-up on the heat exchanger and is a sign the system is overheating in localised spots. It will not always cause immediate failure but it shortens the life of the boiler and should be addressed within a few weeks.
Do you service Viessmann, IBC, Baxi, Laars, and Weil-McLain boilers?
Yes. BC Wide is one of the few HVAC companies in the Lower Mainland with deep experience on European and high-end North American boilers including Viessmann, IBC, Baxi, Laars, Weil-McLain, NTI, Navien and Rinnai. We carry common parts in the truck.
Should I repair or replace my old boiler?
A useful rule: if the boiler is more than 15 years old and the repair cost is more than 50% of replacement, replacement is the better investment. BC Wide will give you both a repair quote and a replacement quote and let you decide.
What HVAC services does BC Wide offer in Metro Vancouver?
BC Wide installs, services and repairs boilers, furnaces, heat pumps, hot water tanks, tankless water heaters, gas fireplaces and air conditioning across Metro Vancouver. We work on residential homes, townhouses, condos with strata systems, and small commercial buildings.
How long has BC Wide been in business?
BC Wide Heating & Air Conditioning has been serving the Greater Vancouver area since 1999. Our TSBC-licensed technicians have built a reputation as some of the most experienced furnace, boiler and heat-pump specialists in the Lower Mainland.
What areas do you serve?
We cover all of Metro Vancouver: Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Delta, Langley, Port Moody, Port Coquitlam, White Rock, Pitt Meadows, and Maple Ridge.

What Greater Vancouver homeowners say about BC Wide

Verified Google reviews — 4.7 average across 181+ ratings
★★★★★
"Alan and Mo were amazing today. They seamlessly replaced our furnace and tankless hot water tank in record time."
Mebz Esmail
Google review · Aug 2026
★★★★★
"Alan and his colleague are very friendly and professional. They installed everything and left it clean."
Laura E. Martínez Urrutia
Google review · Aug 2026
★★★★★
"I have been using BC Wide HVAC Services for over five years for my annual maintenance."
Thor Campbell
Google review · Aug 2026
★★★★★
"Excellent service from start to finish! B.C. Wide is knowledgeable, very professional and showed up on time! I highly recommend this company."
Mark Bouffard
Google review · Aug 2026
★★★★★
"I found these guys on Google. I just moved into a place where no maintenance has been done in the last 6 years."
Thomas Lee
Google review · Aug 2026
★★★★★
"Heat pump, furnace and tankless water heater installed. Competitive price. Careful, friendly, competent, efficient installation team. Professional appearing installation. Good company, highly recommended."
Thomas T
Google review · Jul 2026

Get a Free Quote — Right From This Page

Request a Free Quote

We'll call you back fast — usually within a few hours.
✓ Thanks! We've received your request and will call you back shortly.

Get Comfortable — Talk to BC Wide Today

Free, no-obligation quotes. TSBC-licensed local technicians serving Greater Vancouver since 1999.

Licensed & Insured: Technical Safety BC Licensed Gas Contractor LGA0090068  ·  Class B Gas Licence CGA0028029  ·  Red Seal Technicians  ·  Serving Greater Vancouver since 1999
🔥 Emergency Service(604) 473-9690
📞Call NowFast Response ✉️Email UsGet A Quote