Lochinvar boiler error code E15 means the outlet water got hotter than the manual-reset high limit allows, so the boiler has latched itself off until someone resets it (confirm against the manual for your unit). In practice you lose heat, and hot water too if the boiler heats your tank. Check power, the gas valve and the thermostat, and reset once only if your manual allows it. If E15 comes back, stop resetting: it points to a water-flow or control fault that needs a licensed technician.
If your Lochinvar boiler is showing E15 (Manual Reset High Limit), here’s exactly what it means and what to do. This guide is part of our full Lochinvar boiler error code list.
Severity: Critical — likely no heat / lockout.
What E15 means on a Lochinvar boiler
The outlet water temperature exceeded the manual-reset high limit, which latches the boiler off until reset.
Common causes
- No or low water flow through the boiler
- Failed or air-locked circulator pump
- Closed valve / air lock in the system
- Faulty high-limit or sensor
What you can safely check first
- Check the system pressure gauge and top up via the filling loop to normal pressure if you know how
- Make sure zone/radiator valves are open
- Press the manual-reset high-limit button and RESET once; if it recurs, call a technician
Only attempt the basics above. Do not open the gas train, burner compartment or control wiring.
When to call a technician
This is a fault that should be diagnosed by a licensed technician. Repeated lockouts on a Lochinvar boiler usually point to a real fault that will keep recurring until it’s fixed properly — and continually resetting power can hide a safety issue.
BC Wide Heating & Air Conditioning has serviced Greater Vancouver boilers since 1999. Diagnostics and repairs are carried out by our own Technical Safety BC–licensed technicians (gas contractor licence LGA0090068, Class B Gas Licence CGA0028029) — never subcontractors — and we’re rated 4.7★ across 180+ Google reviews. Honest pricing and free written quotes on replacements.
Lochinvar boiler repair across Greater Vancouver
If a Lochinvar boiler showing E15 won’t reset or has locked out, don’t keep cycling the power — you can mask a real fault or a safety condition. BC Wide provides fast boiler repair and emergency HVAC service 7 days a week throughout the Lower Mainland. Call 604-473-9690 or email info@bcwide.ca and a licensed technician will diagnose the real cause and get your heat & comfort back. See our emergency HVAC service.
Related Lochinvar boiler codes
- Lochinvar boiler E00 — Invalid Lockout
- Lochinvar boiler E01 — Memory Lockout
- Lochinvar boiler E02 — Fan Speed Fault
- Lochinvar boiler E04 — Flow Switch Fault
- Lochinvar boiler E05 — Flame Out of Sequence
- Lochinvar boiler E06 — Auto Reset High Limit
Frequently asked questions
Is E15 on a Lochinvar boiler serious?
It’s a lockout/safety code — the boiler has shut down and needs prompt diagnosis. BC Wide repairs Lochinvar boilers 7 days a week across Greater Vancouver.
How do I reset a Lochinvar boiler after E15?
You can try one power cycle at the breaker/switch after checking the filter and thermostat. If the code returns, stop resetting it and book a licensed technician — a recurring code is a real fault, not a glitch.
Lochinvar boiler error code E15: what it means for you at home
On the existing meaning, E15 is the Manual Reset High Limit: the water leaving the boiler ran hotter than the high-limit safety allows, and the boiler shut itself down and latched off. Confirm against the manual for your unit, because display wording can differ between control generations. The important word is latched. Most boiler faults clear on their own once the condition passes. A manual-reset high limit does not. It deliberately keeps the burner off until a person resets it, because the boiler has decided that something on the water side went wrong and someone should look before it fires again.
For you, that means three things. First, heat: radiators, baseboard convectors, in-floor loops or a hydronic air handler will go cold and stay cold. Second, hot water: if your Lochinvar also heats an indirect hot water tank, the tank will slowly run out, so showers turn lukewarm within hours. Third, safety: the boiler has done its job by shutting down. E15 on its own is not a gas leak or a carbon monoxide warning, but water that overheats inside a sealed system can build pressure and stress the heat exchanger, and the relief valve may discharge. That is why the lockout exists and why it should not be reset over and over.
The owner-words version is simple. The boiler got too hot because the water was not carrying the heat away fast enough, or because the part that measures the temperature is giving a false reading. Our job on a visit is to find out which, and fix the reason rather than the symptom.
- The house is cold and the thermostat is calling, but the boiler is silent with E15 on the display
- The boiler ran, the pipes near it got very hot, then it shut off and will not restart
- Radiators upstairs are cold while the pipes beside the boiler feel hot
- You hear gurgling, banging or a kettle-like rumble from the boiler or pipes before the lockout
- Hot water from the indirect tank is fading or gone
- Water is dripping from the pressure relief valve discharge pipe
- E15 clears after a reset, then returns within hours or days
Lochinvar boiler error code E15: likely causes, most common first, and what you can check
In our experience servicing hydronic systems across Greater Vancouver, E15 is almost always a flow problem before it is a parts problem. The burner is doing exactly what it was told; the water just is not moving through the heat exchanger fast enough to take the heat away. The table below lists the usual causes in roughly the order we find them, what an owner might notice, what an owner can safely check, and the point where it becomes a call for a licensed technician.
Owner-safe checks are limited on purpose. You may confirm the boiler service switch is on and the breaker has not tripped, confirm the gas supply valve to the boiler is open (on most lever valves the handle runs in line with the pipe when open), confirm the thermostat is set to heat and calling, read the pressure gauge without adjusting anything, look at the outside intake and exhaust terminals for snow, leaves or nests, and look at the visible condensate drain line for a kink or blockage. You may press reset once, and only if your owner manual tells you how. Do not open panels, do not touch the gas valve on the appliance, do not bypass or jumper the high limit, and do not keep resetting.
Vent terminals and condensate drains are not the usual cause of E15, since it is a water-side lockout, but a quick look from outside takes a minute and rules them out. A blocked terminal or drain is a common reason for other lockouts, and they are worth noting for the technician.
| Likely cause (most common first) | What you might notice | Owner-safe check | When it becomes a licensed call |
|---|---|---|---|
| 1. Low or no water flow: an isolation valve left closed, a zone valve stuck shut, or a blocked strainer | Boiler fires briefly, pipes beside it get very hot, house stays cold | Confirm any radiator or zone valves you know of are open; note recent work on the system | Any valve you cannot identify, a zone valve that will not open, or a strainer that needs cleaning |
| 2. Circulator pump seized, failed or air-locked | Humming with no water movement sound, or no sound from the pump at all | Listen near the pump while the thermostat calls; do not open or tap it | Always: pump electrical testing, freeing or replacement is technician work |
| 3. Air in the system or low system pressure | Gurgling, cold tops on radiators, gauge reading lower than usual | Read the gauge and write down the number; top up only if your installer showed you how | Pressure that keeps dropping means a leak or a failing expansion tank |
| 4. Sludge, magnetite or debris restricting the heat exchanger | Kettling or banging, slow warm-up, dark water if a radiator is bled | Note the noises and when they happen; nothing to open | Flushing, cleaning, inhibitor and a dirt separator are licensed work |
| 5. Faulty outlet sensor, high-limit device or control wiring | E15 even though water seems to be moving, often at random times | One reset only if the manual allows it | Meter testing of sensors and controls is technician work |
| 6. Settings or piping changed during a renovation or a past repair | E15 started soon after other work on the house or heating | Tell us what changed and when | Re-checking the piping layout and re-commissioning the controls |
When an E15 lockout becomes a licensed call, and the safety line
If you have done the owner-safe checks and pressed reset once, and E15 returns, the boiler is telling you the fault is real. From here it is a licensed call. Gas work and most electrical work on a boiler is restricted in BC to licensed trades, and the parts most often involved in E15 sit behind panels that carry line voltage and connect to the gas train. Repeated resets do not fix anything. Each one lets the boiler fire into the same flow problem, overheat again and trip again, and every cycle adds stress to the heat exchanger and the relief valve.
Call sooner rather than later if the relief valve is discharging water, if you see water on the floor around the boiler, if the pressure gauge is climbing well above its usual reading, if you hear loud banging from the heat exchanger, or if the boiler room smells hot or scorched. Those signs mean the boiler should stay off until it has been checked.
Gas and carbon monoxide safety comes first, always. If you smell gas (a rotten-egg odour) or a carbon monoxide alarm sounds, do not reset the boiler, do not flip switches and do not use your phone inside. Leave the house with everyone, then call FortisBC or 911 from outside. Every home with a gas boiler should have working CO alarms near sleeping areas and on each level, and they should be tested regularly. A boiler that has been overheating should also have its combustion and venting checked as part of the repair, not just its water side.
How our Lochinvar boiler E15 repair visit works, step by step
Diagnostic service calls are $189.00. That covers a licensed technician coming to your home, finding the actual cause of the E15 lockout and explaining it to you in plain language. We come same-day where we can, depending on the day’s workload and where you are in Greater Vancouver; we will tell you honestly when we can arrive and we do not promise a guaranteed window.
Here is what the visit looks like from the moment we arrive. It is the same process our technicians follow on every hydronic lockout, whatever the boiler brand.
- We ask what you saw: when E15 first appeared, how many resets were tried, whether there was noise, a pressure change or recent work on the house.
- We check the gas and venting first: gas supply, intake and exhaust terminals, and the condensate drain, so the boiler is safe to fire for testing.
- We read the system pressure and look at the expansion tank, the relief valve and the fill arrangement.
- We prove water flow: we confirm the circulator is actually moving water, check every isolation and zone valve, and measure the temperature rise across the boiler while it runs.
- We test the outlet sensor and the high-limit circuit with proper meters, comparing the readings against manufacturer-published values for your model rather than guessing.
- We check the control settings and the near-boiler piping layout, because a boiler piped or set up incorrectly can trip its high limit even with healthy parts.
- We look at the water condition: a quick sample from a bleed point tells us whether sludge or magnetite is part of the story.
- We explain the cause and give you a written quote before any work beyond the diagnosis. Nothing gets replaced until you have approved it in writing.
- After the repair we test the safeties: we confirm the high limit trips and latches as it should, confirm flow and pressure are stable, and run the boiler through a full heating cycle before we leave.
Repair or replace an older Lochinvar boiler after repeated E15 lockouts
Most E15 lockouts end in a repair, not a replacement. A seized circulator, a stuck zone valve, an air lock or a failed sensor are all fixable, and a boiler with a sound heat exchanger has a lot of life left after them. Where the conversation changes is when E15 is one symptom of a bigger picture on an older boiler.
These are the questions we work through with you on site. Is the heat exchanger clean and sound, or has years of sludge and repeated overheating left it restricted or damaged? On condensing boilers the heat exchanger is the heart of the appliance and one of the more expensive parts to replace, so its condition carries a lot of weight. Is the boiler near or past the service life the manufacturer publishes for it? Are parts for your control generation still readily available? Has the system needed repeated repairs in recent seasons? Is the near-boiler piping designed in a way that will keep causing flow problems no matter what parts go in?
If repair makes sense, we say so and quote the repair. If replacement makes more sense, we explain why in plain terms and you decide. The in-home estimate for a replacement or new installation is free. If you go ahead with a replacement or new installation through BC Wide, the $189.00 diagnostic charge is waived and taken off the installation. A replacement is also the right moment to correct the root causes of E15: proper primary and secondary piping, a dirt separator and magnetic filter, an air separator, correct inhibitor treatment and a properly sized expansion tank.
We are an independent contractor and we will give you a straight answer either way. Squeezing a few more seasons out of a sound boiler is often the better choice, and we will tell you when that is the case.
Lochinvar boiler E15 service near me: Greater Vancouver areas and boiler brands we cover
BC Wide is based in Burnaby and has worked on boilers across the region since 1999. Metro Vancouver’s water is soft, so hydronic trouble here is rarely limescale. It is sludge, magnetite and corrosion debris that builds up over time, especially in systems that have been topped up with fresh water many times because of a slow leak. That debris is one of the main reasons we see E15 on otherwise healthy boilers.
Vancouver: many older houses on the west side and east side still run hot-water radiators, and quite a few have had a modern condensing boiler connected to piping that was laid out decades ago. That mix of old cast-iron radiators and a low-water-content boiler is a common source of flow lockouts. Burnaby: our home base, with everything from older single-family homes on hydronic heat to townhouse and strata buildings where each unit or the whole building runs on a boiler. Surrey and Langley: newer subdivisions often have in-floor radiant heat, where a closed zone valve or air in a long floor loop can starve the boiler of flow. Richmond and Delta: many homes and townhouses use boilers for radiant floors and indirect hot water, and we often find the boiler sharing duty between space heating and the tank.
The Tri-Cities: Coquitlam, Port Coquitlam and Port Moody have a wide mix of housing, from older split-levels with baseboard convectors to hillside homes with multiple zones. The North Shore: in North Vancouver and West Vancouver, larger hillside homes often carry several heating zones and long pipe runs, and heavy rain and fallen leaves make terminal and drain checks part of every visit. New Westminster: older homes with converted heating systems and plenty of strata buildings, where access, building rules and shared mechanical rooms shape how a repair is scheduled.
In strata buildings, we coordinate with the strata or building manager where shared equipment or access is involved, and we keep the owner informed in writing.
Brands we service on hydronic boilers include Lochinvar, IBC, Navien, Viessmann, Weil-McLain, Triangle Tube, Buderus and Bosch. We are an independent contractor that services these brands, not a factory-authorized dealer or warranty centre for any of them.
More questions homeowners ask
What does Lochinvar boiler error code E15 mean?
E15 means the outlet water temperature went above the manual-reset high limit, and the boiler latched itself off until it is reset. Confirm the exact wording against the manual for your unit. It usually points to poor water flow through the boiler, such as a closed valve, a failed circulator, air in the system or sludge, or to a faulty sensor or high-limit device.
Can I reset a Lochinvar boiler showing E15 myself?
Yes, once, and only if your owner manual explains how to do it. Before you reset, confirm the power is on, the gas supply valve is open and the thermostat is calling for heat. If E15 comes back after that single reset, stop and call a licensed technician, because the fault is real and repeated resets can stress the heat exchanger.
Is it safe to run my Lochinvar boiler after an E15 reset?
If it resets and runs normally with steady pressure and no noise, keep an eye on it and book a check, because E15 rarely happens without a reason. If it locks out again, if the relief valve discharges or if you hear banging, leave it off until a technician has checked it. If you ever smell gas or a CO alarm sounds, leave the house and call FortisBC or 911 from outside.
Why does my Lochinvar boiler keep going to E15?
A repeating E15 almost always means the water is not carrying heat away from the boiler fast enough. The common reasons are a failing or air-locked circulator pump, a zone valve that does not open, low system pressure or sludge restricting the heat exchanger. Less often it is a faulty outlet sensor, high-limit device or a piping layout that never gave the boiler enough flow.
Do you fix Lochinvar boiler E15 near me in Greater Vancouver?
Yes. BC Wide services Lochinvar boilers across Vancouver, Burnaby, Surrey, Richmond, Coquitlam, the Tri-Cities, the North Shore, New Westminster, Delta and Langley. We come same-day where we can, and we will tell you honestly when we can arrive. Call (604) 473-9690 to book.
Can an E15 lockout damage my boiler or hot water tank?
One lockout does no harm; it is the safety doing its job. Repeated overheating from constant resetting can stress the heat exchanger, gaskets and relief valve over time, and if the boiler heats an indirect tank your hot water will run out while it is locked off. Fixing the underlying flow or control fault is what protects the equipment.
- Lochinvar Boiler Code E08 — Heat Exchanger Limit | BC Wide
- Lochinvar Boiler Code E09 — Auxiliary Limit | BC Wide
- Lochinvar Boiler Code E11 — No Flame Running (Flame Fail) | BC Wide
- Lochinvar Boiler Code E12 — No Flame Ignition (Ignition Failure) | BC Wide
- Lochinvar Boiler Code E13 — Flue Temperature Limit | BC Wide
- Lochinvar Boiler Code E18 — Outlet Sensor Differential | BC Wide
- Lochinvar Boiler Code E19 — Flue Sensor Open/Short | BC Wide
- Lochinvar Boiler Code E21 — Outlet Sensor Open/Short | BC Wide
- Lochinvar Boiler Code E22 — Inlet Sensor Open | BC Wide
- Lochinvar Boiler Code E23 — Inlet Sensor Short | BC Wide
Frequently asked questions
How often should a boiler be serviced?
How much does a new boiler cost in Vancouver?
How long does a boiler last?
My boiler is making a banging or kettling noise. Is that dangerous?
Do you service Viessmann, IBC, Baxi, Laars, and Weil-McLain boilers?
Should I repair or replace my old boiler?
What HVAC services does BC Wide offer in Metro Vancouver?
How long has BC Wide been in business?
What areas do you serve?
What Greater Vancouver homeowners say about BC Wide
Get a Free Quote — Right From This Page
Request a Free Quote
Get Comfortable — Talk to BC Wide Today
Free, no-obligation quotes. TSBC-licensed local technicians serving Greater Vancouver since 1999.