Key takeaways

  • The Lochinvar FTXL is a condensing fire-tube gas boiler family; a correct install is decided by heat loss, emitters and domestic hot water demand, not by the size of the old boiler.
  • Venting, condensate neutralizing, gas supply sizing and near-boiler piping are the four places where installs most often go wrong.
  • Metro Vancouver water is soft, so the risk in older hydronic systems is sludge and corrosion, which is why the old system is cleaned and protected before the new boiler is connected.
  • Every gas boiler installation needs a TSBC gas permit, and commissioning should include a combustion analysis recorded on paper.
  • Capacities, vent lengths and clearances are manufacturer-published: check the rating plate and the installation manual for your exact unit.
  • BC Wide installs and services the FTXL family as an independent TSBC-licensed contractor, not as a factory-authorized dealer.

A proper Lochinvar FTXL Boiler installation starts with a room-by-room heat-loss calculation and a survey of your existing piping, venting route and gas supply, then follows a set sequence: remove the old boiler, clean and protect the system water, set the FTXL, pipe it with correct separation and air elimination, run approved venting and a neutralized condensate drain, confirm the gas line can carry the load, wire the controls, and commission it with a combustion analysis before the TSBC gas inspection. The FTXL is a condensing fire-tube gas boiler, so it rewards careful setup: low return water temperatures, a sensible outdoor reset curve and clean water let it condense and modulate the way it was designed to. If any of those steps are skipped, the boiler still fires, but it short-cycles, clogs or wears out sooner. This page explains each step as we do it in Burnaby, Vancouver and across the Lower Mainland, and what you should have in your hands when the job is finished.

What does a correct Lochinvar FTXL Boiler installation involve?

The FTXL is a condensing boiler built around a fire-tube heat exchanger, and it is usually chosen for larger homes, homes with a lot of radiation, or homes where the boiler also heats domestic water through an indirect tank. Because it modulates its firing rate and relies on cool return water to condense, the installation is as much about the system around the boiler as the boiler itself.

On a typical Lower Mainland job the work runs in this order. Each step has a reason, and skipping one usually shows up months later as noise, cycling or a nuisance lockout.

  • Site survey and heat-loss calculation, then a written quote that names the scope.
  • TSBC gas permit pulled before the work starts.
  • Isolate, drain and remove the old boiler; cap and make safe the gas connection.
  • Clean the existing system water and add a dirt and magnetite separator where the old piping warrants it.
  • Set the FTXL on a level base with the manufacturer-published service clearances.
  • Pipe the near-boiler loop, air elimination, expansion tank, pumps and zoning.
  • Run the vent and combustion air using a material and route the installation manual approves.
  • Install the condensate drain with a neutralizer.
  • Connect and test the gas supply; wire power, thermostats, outdoor sensor and any indirect tank.
  • Fill, purge air, commission, run a combustion analysis and set the reset curve.
  • TSBC gas inspection, then handover with documents and a walkthrough.

How do you size a Lochinvar FTXL for a Metro Vancouver house?

Sizing comes from a heat-loss calculation of the house as it is today, not from the rating plate of the boiler coming out. Many older Vancouver and Burnaby homes have had new windows, added insulation or a finished basement since their original boiler was installed, and that original boiler was often oversized to begin with. Matching the old number usually means buying a boiler that spends most of the year cycling on and off at low load.

We measure the rooms, note the walls, windows and ceilings, and look at the design outdoor temperature for your municipality. We then compare the heat loss with what your emitters can actually deliver: cast-iron radiators, baseboard convectors, in-floor radiant or a mix. Emitters decide the water temperature the system needs on a cold day, and that decides how much of the season the FTXL can spend condensing.

Domestic hot water matters too. If the FTXL will also heat an indirect tank, the size and recovery of that tank, and whether it gets priority over space heating, are part of the sizing conversation. The firing range and turndown of each FTXL size are manufacturer-published; check the rating plate and the installation manual for your exact unit rather than relying on a general figure.

What do you check during the site survey before quoting?

A written quote is only as good as the survey behind it. These are the items we look at in the mechanical room and around the house before we price an FTXL install or replacement.

Survey itemWhat we checkWhy it matters
Heat loss and emittersRoom sizes, envelope, radiator and baseboard lengths, radiant zonesSets the boiler size and the water temperature the system really needs
Existing pipingPipe material, condition, zoning method, signs of sludge or leaksDecides whether cleaning, a separator or partial repiping is needed
Vent routeWall or roof termination options, distances to windows, doors, soffits and property linesVent material, length and termination must match the installation manual and the gas code
Old chimneyWhether a gas water heater still shares the chimney after the boiler leavesAn orphaned water heater on an oversized chimney may need a liner or a different vent
Gas supplyMeter capacity, pipe size and length back to the meter, other gas appliancesA condensing boiler that is starved of gas will not light or run reliably
CondensateA floor drain, laundry standpipe or need for a condensate pumpCondensate is acidic and must be neutralized and drained correctly
Electrical and controlsA dedicated circuit, existing thermostats, zone controls, outdoor sensor locationControls and wiring are what let the boiler modulate instead of cycle
AccessStairs, door widths, crawlspace or tight basement roomAffects how the old boiler comes out and the new one goes in

How are venting, condensate and the gas line handled on an FTXL?

Venting is the part of the job we treat most carefully. A condensing boiler produces cool, wet flue gas that cannot go up an old masonry chimney as it is. The FTXL uses a sealed combustion vent and air intake in a material and configuration approved in its installation manual. Allowable vent lengths, number of elbows, termination kits and clearances are manufacturer-published, and they are not something to estimate. On Lower Mainland lots, the termination has to clear windows, doors, air intakes, soffits, walkways and the neighbour’s property, and in tight side yards that often pushes us to a roof termination or a different wall.

Condensate comes off the heat exchanger and the vent continuously while the boiler condenses. It is mildly acidic, so it runs through a neutralizer before it reaches a floor drain or a condensate pump. The neutralizer media is consumed over time and needs checking at each service. Condensate lines also need a trap as the manual shows and a route that will not freeze, which matters for any line passing through an unheated garage or crawlspace.

The gas line is the most common hidden blocker in older homes. A large-capacity boiler added to a house that already has a gas range, a fireplace and a water heater can exceed what the existing piping or meter can deliver. We calculate the load against pipe size and length, and if the line is undersized we quote a new run back toward the meter. Gas piping work is licensed work in BC and is covered by the same permit and inspection.

What near-boiler piping, air elimination and zoning does an FTXL need?

The near-boiler piping decides whether the boiler sees the flow it expects. Most FTXL installs we do use primary and secondary piping or a hydraulic separator so the boiler pump and the system pumps do not fight each other. The exact piping diagrams, pump requirements and flow limits are manufacturer-published; we follow the diagram in the installation manual that matches your system type.

Air and dirt removal come next. A microbubble air eliminator, a properly located expansion tank and a dirt and magnetite separator protect the heat exchanger and keep radiators from gurgling. For zoning we use either zone valves or zone pumps depending on what is already in the house and how the rooms are used, and we label every zone at the manifold so the next technician can read it.

If there is an indirect tank, it gets its own piping and control connection so domestic hot water can take priority for a short time without leaving the house cold.

How does replacing an older boiler with an FTXL work?

Replacement adds a few steps a new build does not have. The old boiler, often a cast-iron atmospheric unit, is drained, disconnected, and taken out. Then the system water gets attention. Decades of operation leave black iron oxide sludge in radiators and piping, and a new boiler with smaller water passages is less forgiving of that than the heavy cast iron it replaces. We flush the system, add a separator, and fill with treated water and an inhibitor suitable for the boiler, as the installation manual specifies.

Removing an atmospheric boiler can also change the chimney. If a gas tank water heater stays behind on a chimney sized for two appliances, it may no longer draft properly, so we check it and quote a liner or a new vent path if needed. We also look for old radiator valves that will not shut, leaking bleed screws and any piping that was patched over the years. Where something is failing, we tell you before it is buried behind the new install, and we write it into the quote rather than surprise you on the day.

What is different about installing an FTXL in Metro Vancouver?

Our winters are mild and wet, with long stretches just above freezing and short cold snaps. That is good news for a condensing boiler: with an outdoor sensor and a well-set reset curve, the FTXL can run at low water temperatures for most of the season and only push hotter water on the coldest nights. Setting that curve for your emitters is one of the most valuable things we do at commissioning.

Metro Vancouver’s water is soft. Hydronic problems here are rarely limescale; they are sludge and corrosion, especially in older systems with steel or iron components or oxygen getting in through non-barrier tubing. That is why cleaning, separation and inhibitor get so much attention on our replacements.

Much of the housing stock is older, with basement mechanical rooms, tight stairs and chimneys that were built for atmospheric equipment. Townhouses and strata buildings add another layer: vent terminations and exterior penetrations often need approval, and we ask owners to check the bylaws and get approval from their strata council before we schedule. For homes with a heritage designation, questions about exterior changes go to the municipality. The gas permit itself comes from Technical Safety BC, and the gas work is inspected under that permit.

What should commissioning and the handover paperwork include?

Commissioning is where an installation becomes a working heating system. After filling and purging air, we check gas pressure at the appliance, light the boiler, and run a combustion analysis at high and low fire, adjusting only as the installation manual allows. We confirm the vent and condensate are working, set the outdoor reset curve, domestic hot water priority and zone operation, and run every zone to temperature.

At the end of the job you should see these documents or records. If a contractor cannot provide them, ask why.

Document or recordWhat it shows
TSBC gas permit numberThe installation was permitted and is subject to inspection
Combustion analysis printout or recordFlue readings at high and low fire, including carbon monoxide
Gas pressure readingsSupply pressure at the appliance under load
Control settings sheetReset curve, maximum supply temperature, hot water priority and zone setup
Water treatment recordHow the system was cleaned and what inhibitor was added
Installation manual and warranty registration detailsThe manufacturer’s documentation for your exact unit; warranty terms are the manufacturer’s
Piping and zone labelsWhich valve, pump and thermostat serves which part of the house

When should you call a licensed technician, and should you repair or replace?

In BC, installing, connecting, adjusting or venting a gas boiler is licensed gas work. Wiring the boiler and its controls is also licensed work in most cases. A homeowner can keep the area around the boiler clear, read the pressure gauge, reset a thermostat, bleed a radiator with a key, and keep CO alarms tested. Anything involving gas, vent, burner, combustion settings or the boiler’s internal controls belongs with a licensed technician.

Call us if the boiler locks out repeatedly, the condensate line backs up, you hear loud kettling or banging, pressure keeps dropping or climbing, or radiators stay cold while the boiler runs. Same-day service is something we offer where we can, depending on the schedule and parts on hand; we will not promise an arrival window we cannot keep.

Whether to repair or replace comes down to the age and condition of the existing boiler, the cost and availability of the failed part, the state of the heat exchanger and piping, and whether the current boiler was badly sized to begin with. A heat exchanger or control board is among the more expensive parts on any condensing boiler, so we look at the whole system before recommending a part. Call (604) 473-9690 and ask for a written quote before any work starts.

Gas & carbon-monoxide safety: A Lochinvar FTXL burns natural gas and produces carbon monoxide inside the appliance. Install a working CO alarm on every level of the home and near sleeping areas, and test them regularly. Never block the vent or combustion air terminations, and keep snow, leaves and plantings clear of them. If you smell gas, do not operate switches, phones or appliances inside; leave the building, then call FortisBC and a licensed gas contractor from outside. If a CO alarm sounds or anyone has headaches, dizziness or nausea at home, get everyone outside into fresh air and call 911. Never use a gas oven, stovetop, barbecue or patio heater indoors for warmth. Gas and venting work must be done by a TSBC-licensed gas fitter under permit.

Frequently asked questions

Can I replace my old boiler with an FTXL of the same size?

Not without a heat-loss calculation first. Many older Metro Vancouver boilers were oversized, and homes have often been upgraded since. Sizing to the old rating plate usually leads to short-cycling and lost efficiency, so we size from the house and the emitters.

Can the FTXL vent into my existing chimney?

Not as the chimney stands. A condensing boiler needs a sealed vent in a material and configuration approved in the installation manual, and the flue gas is too cool and wet for an unlined masonry chimney. Some installations run approved venting through a chase or chimney, but that is decided on site against the manual and the gas code.

Does an FTXL installation need a permit in BC?

Yes. Installing a gas boiler requires a gas permit through Technical Safety BC, and the work is subject to inspection. Ask your contractor for the permit number and keep it with your home records.

Why does my new condensing boiler have a drain line?

The FTXL makes condensate when it runs efficiently, which is a sign it is condensing as designed. That water is mildly acidic, so it passes through a neutralizer and then to a drain or condensate pump. The neutralizer should be checked at each annual service.

Is BC Wide a Lochinvar dealer or warranty centre?

No. BC Wide Home Services is an independent TSBC-licensed contractor that installs and services the Lochinvar FTXL family, among other brands. Warranty terms and claims follow the manufacturer’s published policy, and we help you keep the records that process usually needs.

How long does an FTXL replacement take?

It depends on how much piping, venting and gas line work the survey turns up, and on access to the mechanical room. A straightforward swap is shorter than one that needs a new vent route, a gas line upgrade or a full system flush. We give you the expected timing in the written quote and plan so the house is without heat for as little time as possible.

What maintenance does an FTXL need after installation?

An annual service by a licensed gas technician is the usual recommendation: combustion analysis, heat exchanger and burner inspection, condensate trap and neutralizer check, and a look at system water quality and pressure. Follow the maintenance schedule in the installation manual for your exact unit.

BC Wide Home Services — Lower Mainland home-comfort specialists since 1999

Technical Safety BC Licensed Gas Contractor (LGA0090068) · Class B Gas Licence (CGA0028029) · Red Seal technicians · Evening and weekend calls · Diagnostic service calls $189.00 · Free in-home estimates on replacements (the $189.00 is waived if you replace with us). Call 604-473-9690 or book a free replacement estimate.

4.7★181+ Google reviews
27+Years serving Greater Vancouver
20+Brands serviced
$0Free written estimates on installs

Frequently asked questions

How often should a boiler be serviced?
Annual servicing is recommended for all residential boilers. BC Wide's annual service includes combustion analysis, heat exchanger inspection, expansion tank pressure check, condensate trap cleaning, and a full safety check. Annual maintenance is also required to keep most manufacturer warranties valid.
How much does a new boiler cost in Vancouver?
A typical residential high-efficiency gas boiler in Metro Vancouver costs $7,500–$15,000 installed, depending on size, brand, and whether the system is heating only or a combi unit that also handles hot water. BC Wide provides a free written quote with three options at different price points.
How long does a boiler last?
A well-maintained cast-iron boiler can last 25–30 years, a modern high-efficiency condensing boiler typically lasts 15–20 years, and a combi boiler 12–18 years. Annual servicing has the single biggest impact on lifespan.
My boiler is making a banging or kettling noise. Is that dangerous?
Kettling (a banging or whistling sound) is usually caused by limescale build-up on the heat exchanger and is a sign the system is overheating in localised spots. It will not always cause immediate failure but it shortens the life of the boiler and should be addressed within a few weeks.
Do you service Viessmann, IBC, Baxi, Laars, and Weil-McLain boilers?
Yes. BC Wide is one of the few HVAC companies in the Lower Mainland with deep experience on European and high-end North American boilers including Viessmann, IBC, Baxi, Laars, Weil-McLain, NTI, Navien and Rinnai. We carry common parts in the truck.
Should I repair or replace my old boiler?
A useful rule: if the boiler is more than 15 years old and the repair cost is more than 50% of replacement, replacement is the better investment. BC Wide will give you both a repair quote and a replacement quote and let you decide.
What HVAC services does BC Wide offer in Metro Vancouver?
BC Wide installs, services and repairs boilers, furnaces, heat pumps, hot water tanks, tankless water heaters, gas fireplaces and air conditioning across Metro Vancouver. We work on residential homes, townhouses, condos with strata systems, and small commercial buildings.
How long has BC Wide been in business?
BC Wide Heating & Air Conditioning has been serving the Greater Vancouver area since 1999. Our TSBC-licensed technicians have built a reputation as some of the most experienced furnace, boiler and heat-pump specialists in the Lower Mainland.
What areas do you serve?
We cover all of Metro Vancouver: Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Delta, Langley, Port Moody, Port Coquitlam, White Rock, Pitt Meadows, and Maple Ridge.

What Greater Vancouver homeowners say about BC Wide

Verified Google reviews — 4.7 average across 181+ ratings
★★★★★
"Alan and Mo were amazing today. They seamlessly replaced our furnace and tankless hot water tank in record time."
Mebz Esmail
Google review · Aug 2026
★★★★★
"Alan and his colleague are very friendly and professional. They installed everything and left it clean."
Laura E. Martínez Urrutia
Google review · Aug 2026
★★★★★
"I have been using BC Wide HVAC Services for over five years for my annual maintenance."
Thor Campbell
Google review · Aug 2026
★★★★★
"Excellent service from start to finish! B.C. Wide is knowledgeable, very professional and showed up on time! I highly recommend this company."
Mark Bouffard
Google review · Aug 2026
★★★★★
"I found these guys on Google. I just moved into a place where no maintenance has been done in the last 6 years."
Thomas Lee
Google review · Aug 2026
★★★★★
"Heat pump, furnace and tankless water heater installed. Competitive price. Careful, friendly, competent, efficient installation team. Professional appearing installation. Good company, highly recommended."
Thomas T
Google review · Jul 2026

Get a Free Quote — Right From This Page

Request a Free Quote

We'll call you back fast — usually within a few hours.
✓ Thanks! We've received your request and will call you back shortly.

Get Comfortable — Talk to BC Wide Today

Free, no-obligation quotes. TSBC-licensed local technicians serving Greater Vancouver since 1999.

Licensed & Insured: Technical Safety BC Licensed Gas Contractor LGA0090068  ·  Class B Gas Licence CGA0028029  ·  Red Seal Technicians  ·  Serving Greater Vancouver since 1999
🔥 Emergency Service(604) 473-9690
📞Call NowFast Response ✉️Email UsGet A Quote