Quick answer

Viessmann boiler error code 20 means the control is reading a short circuit on the flow (supply) temperature sensor, so the boiler cannot tell how hot the water leaving it is. It will usually stop or limit heating and, on units that make domestic hot water, hot water too. Confirm the meaning against the manual for your unit. Check power, the gas valve and the thermostat, reset once only if the manual allows it, then call a licensed technician at (604) 473-9690.

If your Viessmann boiler is showing 20 (Flow (supply) temperature sensor short circuit), here’s exactly what it means and what to do. This guide is part of our full Viessmann boiler error code list.

Severity: Needs attention.

What 20 means on a Viessmann boiler

The flow/supply temperature sensor is reading a short circuit, affecting temperature control.

Common causes

  • Faulty flow temperature sensor
  • Wiring short
  • Control board fault

What you can safely check first

  1. No safe homeowner fix — book an engineer

Only attempt the basics above. Do not open the gas train, burner compartment or control wiring.

When to call a technician

This is a fault that should be diagnosed by a licensed technician. Repeated lockouts on a Viessmann boiler usually point to a real fault that will keep recurring until it’s fixed properly — and continually resetting power can hide a safety issue.

BC Wide Heating & Air Conditioning has serviced Greater Vancouver boilers since 1999. Diagnostics and repairs are carried out by our own Technical Safety BC–licensed technicians (gas contractor licence LGA0090068, Class B Gas Licence CGA0028029) — never subcontractors — and we’re rated 4.7★ across 180+ Google reviews. Honest pricing and free written quotes on replacements.

Viessmann boiler repair across Greater Vancouver

If a Viessmann boiler showing 20 won’t reset or has locked out, don’t keep cycling the power — you can mask a real fault or a safety condition. BC Wide provides fast boiler repair and emergency HVAC service 7 days a week throughout the Lower Mainland. Call 604-473-9690 or email info@bcwide.ca and a licensed technician will diagnose the real cause and get your heat & comfort back. See our emergency HVAC service.

Related Viessmann boiler codes

Frequently asked questions

Is 20 on a Viessmann boiler serious?

It signals a fault to address; left alone it can lead to a no-heat shutdown. BC Wide repairs Viessmann boilers 7 days a week across Greater Vancouver.

How do I reset a Viessmann boiler after 20?

You can try one power cycle at the breaker/switch after checking the filter and thermostat. If the code returns, stop resetting it and book a licensed technician — a recurring code is a real fault, not a glitch.

Viessmann Boiler Error Code 20: what it means for your heat, hot water and safety

In plain terms, Code 20 tells you the boiler has lost a trustworthy reading of its own supply water temperature. The flow sensor sits where heated water leaves the boiler on its way to your radiators, baseboard loops, in-floor heating or indirect hot water tank. The control reads that sensor constantly to decide how hard to fire the burner, when to ease off and when to stop. When the reading looks like a short circuit, the control has no way of knowing the real water temperature, and a well-designed boiler does the cautious thing: it stops or restricts firing rather than guess. Confirm the exact meaning and the boiler’s response against the manual for your unit, because control generations differ in how they react.

For you, that usually means rooms cooling down over a few hours. If the boiler also makes domestic hot water, either as a combi unit or by heating an indirect tank, hot water can drop off as well. The code itself is a protective response. It is not usually a sign that the boiler is about to do something dangerous. The risk comes from what happens next: repeated resets, unplugging and replugging the boiler, or someone poking at wiring inside the casing to get the heat back on.

What homeowners usually notice before they read the display:

  • The house is cooling down even though the thermostat is calling for heat.
  • Radiators or baseboards are lukewarm or cold all over, even late in the day.
  • In-floor heating feels flat and rooms take far longer than usual to recover in the morning.
  • Hot water runs out early or never gets properly hot, on combi units or systems with an indirect tank.
  • The boiler fires briefly, shuts down, and the display shows the code again.
  • The code clears after a power cycle, then comes back hours or days later, often when the boiler is working hardest on a cold night.
  • A fault symbol or light is showing on the display while the circulator pump is still running.

Viessmann boiler error code 20: likely causes, most common first, and what you can check

A short-circuit reading means the control sees far less electrical resistance through the sensor circuit than a working sensor would give at any real water temperature. That narrows the search. The causes below are listed in the order we tend to find them on site, not as a manufacturer ranking, and the meaning should always be confirmed against the manual for your unit.

Most common: the flow temperature sensor itself has failed. Sensors are sealed components that live through many thousands of heating cycles. Over years, internal breakdown or moisture creeping past the seal can drop the reading to a short. The repair is a correct replacement sensor, fitted and seated properly in its well or clip so it reads the water and not the air around it.

Second: moisture or corrosion at the sensor connector. Boilers in Metro Vancouver often sit in damp basements, crawlspace mechanical rooms or strata closets right beside the condensate trap. A slow drip from a fitting, a weeping relief valve or a condensate leak can run along a pipe onto the plug and bridge its contacts. Drying and cleaning the connection can clear the code, but the source of the water has to be found or the fault returns.

Third: damaged or pinched wiring. The harness between the sensor and the control can chafe against a sharp edge, get crushed when a cover is refitted, or be nicked during earlier work. Bare conductors touching each other or the chassis give exactly this reading, and the fault is often intermittent, coming and going with vibration and heat.

Least common: a fault on the control board input. Occasionally the sensor and wiring test fine and the problem is the input on the boiler control itself. A control board is one of the more expensive parts on a boiler, which is exactly why it should only be condemned after the sensor and harness have been tested, never on a guess.

None of these causes can be fixed safely by a homeowner. What you can do is rule out the simple things behind most no-heat calls and give the technician good information. These are the owner-safe checks, and the only ones we recommend:

  • Power: confirm the boiler service switch near the unit is on and the breaker has not tripped. Do not open the boiler casing.
  • Gas supply: make sure the manual shut-off valve on the gas pipe to the boiler is open, with the handle in line with the pipe. Never touch the gas valve inside the boiler.
  • Thermostat: check it is set to heat, set above the current room temperature, and has fresh batteries if it uses them.
  • One reset only, and only if the owner manual for your model describes a reset for this condition. If the code returns, leave the boiler locked out and call.
  • Outside vent terminals: check the intake and exhaust terminals outside are clear of leaves, snow, wasp nests and anything stacked against them. This does not cause Code 20 directly, but it rules out a second problem.
  • Condensate drain: look at the visible drain line and trap for leaks or water pooling under or beside the boiler, and photograph anything you find.
Likely causeWhat you might noticeOwner-safe checkLicensed technician step
Failed flow temperature sensorCode returns soon after every reset and the house stays coldNote when the code appears and whether it clears; do not keep resettingTest the sensor against the manufacturer’s resistance and temperature data and replace it if it is out of range
Moisture or corrosion at the connectorDrips, water marks or rust near the boiler; code worse in damp weatherLook for drips from pipes, the relief valve discharge or the condensate trap without opening the casing; take photosIsolate power, inspect and clean the connector, then find and fix the water source
Pinched or chafed wiringFault comes and goes, sometimes after other work on the boilerTell us about any recent service, renovation or equipment that was movedTrace the harness, test for continuity and shorts, then repair or replace the damaged section
Control board input faultSensor and wiring test fine but the code persistsNone beyond the basic checks aboveConfirm by testing before any board is condemned, then quote the repair in writing

Is it safe to run a Viessmann boiler with error code 20? When it becomes a licensed call

A boiler that has locked out on Code 20 is generally in a safe state: it has stopped or reduced firing because it cannot read its supply temperature. The danger comes from working around that protection. A boiler forced to run without a valid supply temperature reading is exactly the situation the control is designed to prevent, because the burner could keep firing into water that is already too hot. So the honest answer is no: do not try to keep it running, and do not let anyone jumper the circuit, bypass the sensor or fit a random sensor just to get heat back.

It becomes a licensed call as soon as the code returns after the one reset your manual allows, and immediately if any of the signs below apply. In BC, gas work on a boiler must be done by a licensed gas fitter working for a licensed gas contractor, and the electrical work on control and sensor circuits belongs to licensed trades as well. Opening the boiler casing, unplugging sensors, testing circuits and replacing parts are all technician work. The owner’s job is the short list of outside checks, good notes and a phone call.

Gas and carbon monoxide safety: if you smell gas, a rotten-egg odour, or your carbon monoxide alarm sounds, do not touch light switches, the thermostat or the boiler. Get everyone out of the home, then call FortisBC or 911 from outside. Every home with a gas boiler should have working CO alarms near sleeping areas and near the mechanical room, tested regularly. Code 20 is a sensor fault, but any repair visit to a gas boiler should still include a check of combustion, venting and the safety controls.

  • Code 20 comes back after a single permitted reset.
  • Water, rust or corrosion is visible near the boiler wiring, the condensate trap or the relief valve.
  • The boiler is short-cycling, making new noises, or the pressure gauge is reading differently from normal.
  • You smell gas, see soot around the boiler or vent, or a CO alarm has sounded. Leave first, then call FortisBC or 911 from outside.
  • A cold snap is coming and the home cannot hold temperature, especially with young children, elderly family or exposed pipes in the house.

How our Viessmann boiler error code 20 repair visit works

Diagnostic service calls are $189.00. That covers a licensed technician coming to your boiler, finding the actual cause of the code, and explaining it to you before anything else is done. Timing is same-day where we can. In the shoulder seasons that is often possible, but during a cold snap demand rises across the whole region, and we will tell you honestly when our earliest slot is rather than promise an arrival window we cannot keep. This is how the visit runs, step by step:

  • Step one, the call: we ask what the display shows, when the code first appeared, whether it cleared on a reset, and whether anyone has worked on the boiler or the room around it recently. Photos of the display and the area around the boiler help us come prepared.
  • Step two, safety on arrival: the technician checks for gas odour, confirms the CO alarms, and looks over the venting, the condensate system and the area around the boiler before opening anything.
  • Step three, the fault history: where the control keeps a fault log, it shows whether Code 20 has been constant or intermittent, which points toward either a failed sensor or a wiring and moisture problem.
  • Step four, testing with the right meters: with power isolated, the sensor is tested against the manufacturer’s resistance and temperature data for your model, and the harness is checked for continuity and shorts. The control input is checked last, once the sensor and wiring are proven.
  • Step five, the root cause: if moisture is involved, we trace where the water comes from, whether that is a weeping fitting, the relief valve or the condensate trap. Replacing a sensor without fixing a leak only buys time.
  • Step six, a written quote before any work beyond diagnosis: you get the cause, the part involved in general terms, whether a sensor, connector, section of harness or control board, and a written price. Nothing proceeds until you approve it.
  • Step seven, repair and prove it: the boiler is run through a full heating cycle, the supply temperature reading is compared against a reference measurement, the safety controls are tested and combustion is checked, so you know the boiler is running correctly and not just running.
  • Step eight, the paperwork: you should receive in writing what was found, what was replaced, and any follow-up we recommend, such as fixing a slow leak, servicing the condensate trap or cleaning a sludged system.

Repair or replace a Viessmann boiler with code 20? What decides it, and the boiler brands we service

On its own, Code 20 is rarely a reason to replace a boiler. A flow sensor, connector or short length of harness is a modest repair on most units, and a boiler that is otherwise in good shape should simply be repaired. The picture changes when the code is one symptom among several on an older unit.

These are the questions we work through with owners on site. How old is the boiler, and what condition is the heat exchanger in? Has it needed several repairs over recent heating seasons? Are parts for that control generation still readily available? Is the system water full of sludge? That last question matters here: Metro Vancouver water is soft, so hydronic trouble in this region is usually corrosion and dark magnetite sludge rather than limescale, and years of sludge make a boiler work harder and wear components faster. Is the boiler still sized correctly after insulation or window upgrades? And does the household now need more hot water than the current setup delivers?

If the answer is repair, we fix it and tell you what to watch for. If the honest answer is replacement, we explain why. The in-home estimate for replacing or installing equipment is free. If you go ahead with a replacement or new installation through BC Wide, the $189.00 diagnostic charge is waived and taken off the installation. A proper written replacement quote should spell out the boiler proposed, venting and condensate work, any system flushing or filtration, the gas permit, electrical work and removal of the old unit.

Boiler brands we service: Viessmann, IBC, Lochinvar, Buderus, Weil-McLain, Navien, Bosch and Rinnai. We are an independent TSBC-licensed contractor, not a factory-authorized dealer or warranty centre for any of them, so our repair-or-replace advice is not tied to selling one maker’s equipment.

Points toward repairPoints toward replacement
The boiler is otherwise reliable and this is its first serious faultCode 20 is one of several faults over recent heating seasons
Testing shows the sensor, connector or harness is the causeThe control board has failed and parts for that generation are hard to source
Heat exchanger and venting are in good conditionThe heat exchanger shows corrosion, leaks or damage
System water is clean or can be cleaned and protectedLong-term sludge has damaged components and will keep doing so
Heat and hot water have met the household’s needsThe household has outgrown the boiler’s heating or hot water capacity

Viessmann boiler error code 20 service near me: Greater Vancouver coverage and why owners trust BC Wide

We service Viessmann boilers across Greater Vancouver: Vancouver, Burnaby, Surrey, Richmond, Coquitlam and the rest of the Tri-Cities including Port Coquitlam and Port Moody, the North Shore including North Vancouver and West Vancouver, New Westminster, Delta and Langley. Our base is in Burnaby, which keeps most of the region within reasonable reach, although bridge and tunnel traffic at rush hour is a real factor in how quickly we can arrive.

The housing stock shapes what we tend to find. Many older detached homes in Vancouver, Burnaby and New Westminster have had their original heating replaced with a modern condensing boiler connected to existing radiators or baseboard loops, and those older distribution systems can carry sludge and air that make the boiler work hard. Many newer houses and townhomes in Surrey, Langley, Coquitlam and parts of Richmond and Delta use boilers for in-floor radiant heat, sometimes combined with domestic hot water. On the North Shore, hillside homes can have longer venting runs and tight mechanical rooms. Townhome and strata units across the region often put the boiler in a small closet, where access, venting rules and strata approvals all matter when a part or a whole boiler has to be changed.

Our mild, wet coastal climate matters for this particular code. Damp mechanical rooms, condensate leaks and humid air are a steady source of corrosion at electrical connectors, and boilers here work hardest during the short cold snaps, which is exactly when a marginal sensor or connection tends to give up.

Why owners call us for this code: BC Wide Home Services Ltd has worked on Metro Vancouver heating systems since 1999. We are a Technical Safety BC licensed gas contractor, licence LGA0090068, and our gas work is carried out by licensed gas fitters, with our Class B gas licence CGA0028029. Gas work is done under permit where required and we arrange the inspection. You get a written quote before any work beyond diagnosis and a written record of what was found and done.

  • Independent TSBC-licensed contractor: we service many boiler brands and are not a dealer or warranty centre for any of them.
  • Licensed gas fitters on every gas job, with permits and inspections where the work requires them.
  • A written quote before any work beyond diagnosis, so nothing comes as a surprise.
  • Honest timing: same-day where we can, and a straight answer when we cannot.
  • One number for the whole region: (604) 473-9690.

More questions homeowners ask

What does error code 20 mean on a Viessmann boiler?

It means the boiler’s control is reading a short circuit on the flow (supply) temperature sensor, the sensor that measures the water leaving the boiler. Because the control cannot trust that reading, the boiler usually stops or limits heating. Confirm the exact meaning against the manual for your unit, and have a licensed technician test the sensor, the wiring and the control input.

Can I reset Viessmann boiler error code 20 myself?

Only once, and only if the owner manual for your model describes a reset for this condition. If the code comes back, the fault is real and needs testing, and repeated resets or power cycling will not fix a shorted sensor or wire. Leave the boiler locked out and call (604) 473-9690.

Is it safe to run my Viessmann boiler with code 20 showing?

Do not try to force it to run. The lockout is the boiler protecting itself because it cannot read its supply water temperature, and bypassing or jumpering the sensor removes that protection. If you smell gas or a CO alarm sounds, leave the home and call FortisBC or 911 from outside.

What causes a Viessmann flow temperature sensor short circuit?

The most common cause is a failed sensor, followed by moisture or corrosion at the sensor connector, often from a drip or condensate leak nearby. Pinched or chafed wiring is next, and a fault on the control board input is the least common. A licensed technician tests each in turn before any part is replaced.

Is there a charge to diagnose Viessmann boiler error code 20?

Yes. A diagnostic service call applies, and it covers a licensed technician finding the actual cause and explaining it before any repair, with a written quote for anything beyond diagnosis. If the boiler turns out to need replacing and you go ahead with a replacement or new installation through BC Wide, the diagnostic charge is waived and taken off the installation.

Who repairs Viessmann boilers near me in Greater Vancouver?

BC Wide services Viessmann boilers across Vancouver, Burnaby, Surrey, Richmond, Coquitlam, the Tri-Cities, the North Shore, New Westminster, Delta and Langley. We are an independent TSBC-licensed gas contractor, not a Viessmann dealer or warranty centre, and licensed gas fitters do the work. Call (604) 473-9690 and we will book the earliest visit we can, same-day where we can.

4.7★181+ Google reviews
27+Years serving Greater Vancouver
20+Brands serviced
$0Free written estimates on installs

Frequently asked questions

How often should a boiler be serviced?
Annual servicing is recommended for all residential boilers. BC Wide's annual service includes combustion analysis, heat exchanger inspection, expansion tank pressure check, condensate trap cleaning, and a full safety check. Annual maintenance is also required to keep most manufacturer warranties valid.
How much does a new boiler cost in Vancouver?
A typical residential high-efficiency gas boiler in Metro Vancouver costs $7,500–$15,000 installed, depending on size, brand, and whether the system is heating only or a combi unit that also handles hot water. BC Wide provides a free written quote with three options at different price points.
How long does a boiler last?
A well-maintained cast-iron boiler can last 25–30 years, a modern high-efficiency condensing boiler typically lasts 15–20 years, and a combi boiler 12–18 years. Annual servicing has the single biggest impact on lifespan.
My boiler is making a banging or kettling noise. Is that dangerous?
Kettling (a banging or whistling sound) is usually caused by limescale build-up on the heat exchanger and is a sign the system is overheating in localised spots. It will not always cause immediate failure but it shortens the life of the boiler and should be addressed within a few weeks.
Do you service Viessmann, IBC, Baxi, Laars, and Weil-McLain boilers?
Yes. BC Wide is one of the few HVAC companies in the Lower Mainland with deep experience on European and high-end North American boilers including Viessmann, IBC, Baxi, Laars, Weil-McLain, NTI, Navien and Rinnai. We carry common parts in the truck.
Should I repair or replace my old boiler?
A useful rule: if the boiler is more than 15 years old and the repair cost is more than 50% of replacement, replacement is the better investment. BC Wide will give you both a repair quote and a replacement quote and let you decide.
What HVAC services does BC Wide offer in Metro Vancouver?
BC Wide installs, services and repairs boilers, furnaces, heat pumps, hot water tanks, tankless water heaters, gas fireplaces and air conditioning across Metro Vancouver. We work on residential homes, townhouses, condos with strata systems, and small commercial buildings.
How long has BC Wide been in business?
BC Wide Heating & Air Conditioning has been serving the Greater Vancouver area since 1999. Our TSBC-licensed technicians have built a reputation as some of the most experienced furnace, boiler and heat-pump specialists in the Lower Mainland.
What areas do you serve?
We cover all of Metro Vancouver: Vancouver, Burnaby, Richmond, Surrey, Coquitlam, North Vancouver, West Vancouver, New Westminster, Delta, Langley, Port Moody, Port Coquitlam, White Rock, Pitt Meadows, and Maple Ridge.

What Greater Vancouver homeowners say about BC Wide

Verified Google reviews — 4.7 average across 181+ ratings
★★★★★
"Alan and Mo were amazing today. They seamlessly replaced our furnace and tankless hot water tank in record time."
Mebz Esmail
Google review · Aug 2026
★★★★★
"Alan and his colleague are very friendly and professional. They installed everything and left it clean."
Laura E. Martínez Urrutia
Google review · Aug 2026
★★★★★
"I have been using BC Wide HVAC Services for over five years for my annual maintenance."
Thor Campbell
Google review · Aug 2026
★★★★★
"Excellent service from start to finish! B.C. Wide is knowledgeable, very professional and showed up on time! I highly recommend this company."
Mark Bouffard
Google review · Aug 2026
★★★★★
"I found these guys on Google. I just moved into a place where no maintenance has been done in the last 6 years."
Thomas Lee
Google review · Aug 2026
★★★★★
"Heat pump, furnace and tankless water heater installed. Competitive price. Careful, friendly, competent, efficient installation team. Professional appearing installation. Good company, highly recommended."
Thomas T
Google review · Jul 2026

Get a Free Quote — Right From This Page

Request a Free Quote

We'll call you back fast — usually within a few hours.
✓ Thanks! We've received your request and will call you back shortly.

Get Comfortable — Talk to BC Wide Today

Free, no-obligation quotes. TSBC-licensed local technicians serving Greater Vancouver since 1999.

Licensed & Insured: Technical Safety BC Licensed Gas Contractor LGA0090068  ·  Class B Gas Licence CGA0028029  ·  Red Seal Technicians  ·  Serving Greater Vancouver since 1999
🔥 Emergency Service(604) 473-9690
📞Call NowFast Response ✉️Email UsGet A Quote