Weil-McLain boiler error code 24 (shown as _24) is a soft lockout: the control has read return water hotter than outlet water, which usually points to a sensor or water-flow problem such as reversed circulation, a faulty or misplaced sensor, or air trapped in the boiler. It clears on its own once the readings return to normal, so there is nothing to keep resetting. If it keeps coming back, have a licensed gas technician find the cause. Confirm the meaning against the manual for your unit.
If your Weil-McLain boiler is showing _24 (Soft lockout — return hotter than outlet), here’s exactly what it means and what to do. This guide is part of our full Weil-McLain boiler error code list.
Severity: Needs attention.
What _24 means on a Weil-McLain boiler
Soft lockout. The control measured return water hotter than the outlet, which usually points to a sensor or flow issue; it clears automatically when readings normalize.
Common causes
- Sensor placement/fault
- Reversed flow or circulation problem
- Air-bound boiler
What you can safely check first
- No homeowner reset needed — it self-clears
- If it recurs frequently, have a technician check the sensors and circulation
Only attempt the basics above. Do not open the gas train, burner compartment or control wiring.
When to call a technician
This is a fault that should be diagnosed by a licensed technician. Repeated lockouts on a Weil-McLain boiler usually point to a real fault that will keep recurring until it’s fixed properly — and continually resetting power can hide a safety issue.
BC Wide Heating & Air Conditioning has serviced Greater Vancouver boilers since 1999. Diagnostics and repairs are carried out by our own Technical Safety BC–licensed technicians (gas contractor licence LGA0090068, Class B Gas Licence CGA0028029) — never subcontractors — and we’re rated 4.7★ across 180+ Google reviews. Honest pricing and free written quotes on replacements.
Weil-McLain boiler repair across Greater Vancouver
If a Weil-McLain boiler showing _24 won’t reset or has locked out, don’t keep cycling the power — you can mask a real fault or a safety condition. BC Wide provides fast boiler repair and emergency HVAC service 7 days a week throughout the Lower Mainland. Call 604-473-9690 or email info@bcwide.ca and a licensed technician will diagnose the real cause and get your heat & comfort back. See our emergency HVAC service.
Related Weil-McLain boiler codes
- Weil-McLain boiler 0 — Standby — no call for heat
- Weil-McLain boiler 3 — Space heating — burner active
- Weil-McLain boiler 4 — Domestic hot water heating
- Weil-McLain boiler 6 — Burner off — setpoint reached
- Weil-McLain boiler E00 — Flame detected at startup (false flame)
- Weil-McLain boiler E02 — Ignition failed — 5 attempts (no flame)
Frequently asked questions
Is _24 on a Weil-McLain boiler serious?
It signals a fault to address; left alone it can lead to a no-heat shutdown. BC Wide repairs Weil-McLain boilers 7 days a week across Greater Vancouver.
How do I reset a Weil-McLain boiler after _24?
You can try one power cycle at the breaker/switch after checking the filter and thermostat. If the code returns, stop resetting it and book a licensed technician — a recurring code is a real fault, not a glitch.
Weil-McLain boiler error code 24: what it means for your heat and hot water
In plain terms, _24 means the boiler has stopped firing for a while because the temperatures it reads on the water side do not add up. In a healthy hydronic system, water leaves the boiler hot through the outlet (the supply) and comes back cooler through the return after it has given up heat to your radiators, fin-tube convectors, in-floor tubing or an indirect hot water tank. When the control sees the return warmer than the outlet, it reads that as a sign that water is moving the wrong way, is barely moving at all, or that one of its own sensors is giving a false reading. As the code description on this page says, it is a soft lockout that clears automatically when the readings settle. Confirm that meaning against the manual for your unit, because control generations differ.
For you, that usually means heat that comes and goes. The boiler pauses, waits, tries again, and may run normally for hours before the code returns. Rooms can drift cooler, slower zones may never quite catch up on a cold morning, and if your domestic hot water comes from an indirect tank heated by the boiler, showers can run short while the boiler sits in lockout. The code itself is not a gas leak warning or a carbon monoxide alarm. It is the control protecting the heat exchanger from running under conditions it was not designed for. That is exactly why it should not be ignored: a boiler that keeps tripping on a flow-related fault is a boiler that is not moving water properly, and poor flow is hard on a heat exchanger over time.
These are the things homeowners usually tell us when they call about this code, in their own words:
- The display shows _24, the burner is off, and then the boiler starts up again on its own later.
- Some rooms or zones are warm while others stay cold, or one floor never gets comfortable.
- Radiators or the in-floor heat take much longer than usual to warm up.
- There is gurgling, rushing or trickling water noise in the pipes or near the boiler.
- The pump by the boiler sounds louder than usual, or the boiler seems to run with no heat reaching the house.
- Hot water from the indirect tank runs out sooner, or the code seems to show up mostly when the tank is heating.
- The code started right after a repair, a new zone, a pump replacement, a drain-down or a system refill.
- The pressure gauge on the boiler reads differently from what it normally shows.
Weil-McLain boiler error code 24 causes, most common first
The order below reflects what is most commonly found on residential hydronic systems in general. It is not a diagnosis of your boiler, and the cause on your system may sit further down the list. What all of these have in common is that they disturb either the flow of water through the boiler or the accuracy of the two temperature readings the control compares.
1. Air in the boiler or the piping. After a refill, a leak repair or any work that drained part of the system, air pockets can collect in the heat exchanger and high points of the piping. A circulator pushing air cannot move water properly, flow through the boiler stalls, and the sensors start reading odd temperatures. Correct purging, a working air separator and automatic air vents, and the right fill pressure usually settle it.
2. A circulation or flow problem. A weak or failed circulator, a zone valve that is stuck, an isolation valve left partly closed, a plugged strainer or sludge build-up in the heat exchanger can all choke flow. In Metro Vancouver the water is soft, so the restriction we find is almost always sludge and corrosion debris rather than limescale.
3. Reversed flow. A circulator installed facing the wrong way, supply and return lines cross-connected during a replacement, a system pump pushing water backwards through the boiler on a primary-secondary layout, or a failed flow check that lets another zone drive water the wrong way can all make the return genuinely hotter than the outlet. This is common on systems that were modified or added to over the years.
4. A sensor fault or a sensor in the wrong place. Supply and return sensors can be swapped, loose in their wells, damaged, or simply drifting out of tolerance. The water may be flowing perfectly while the control is being fed bad information.
5. A piping design issue. Pumps fighting each other, an indirect tank piped in a way that back-feeds the boiler, or near-boiler piping that does not match the manufacturer’s installation instructions can produce the code under certain calls only. These take the longest to find because the boiler can behave normally most of the time.
| Likely cause (most common first) | What you might notice | Owner-safe check | When it becomes a licensed call |
|---|---|---|---|
| Air in the boiler or piping | Gurgling or rushing water, code soon after a refill or repair, uneven heat | Note the pressure gauge reading and when the noise happens; do not bleed or refill | Any time purging, refilling or air-separator work is needed |
| Weak circulation or blocked flow | Cold zones, slow warm-up, pump louder or quieter than usual | Confirm the thermostat is calling and note which zones stay cold | Pump, zone valve, strainer or sludge work, and any valve adjustment |
| Reversed flow | Code began after a pump change, new zone or replacement work | Write down what work was done and when the code first appeared | Always; flow direction and piping corrections are technician work |
| Sensor fault or misplacement | Code with no obvious heating problem, random timing | Photograph the display each time the code shows | Always; sensors are tested with a meter against the manufacturer chart |
| Piping design issue | Code only on certain calls, such as when the hot water tank is heating | Note whether heat or hot water was calling when it appeared | Always; near-boiler piping is assessed and corrected by a licensed technician |
What can I check myself before calling about Weil-McLain code 24?
Because _24 is described as a self-clearing soft lockout, there is normally nothing for you to reset. Your job is to make sure the basics are in order and to gather the information that will shorten the diagnosis. Stay on the outside of the boiler for all of these. Gas work and most electrical work in BC is legally restricted to licensed trades, and nothing below involves opening the appliance.
Steps a homeowner may safely do:
- Power: make sure the boiler service switch (often a light-style switch near the boiler or at the top of the stairs) is on and the breaker for the boiler has not tripped. If a breaker trips again, leave it off and call.
- Gas supply: check that the yellow-handled gas valve on the line to the boiler is open, with the handle running in line with the pipe. Never move any other valve.
- Thermostat: confirm it is calling for heat by setting it a few degrees above room temperature, and replace the batteries if it uses them.
- Reset: only if your owner manual specifically allows a manual reset, try it once. Do not cycle power over and over; repeated resets hide the pattern a technician needs to see and can mask a safety problem.
- Outside vent terminals: look at the intake and exhaust terminals outside and make sure they are not blocked by leaves, wet debris, snow or a nest. Do not remove or alter the terminal caps.
- Condensate drain: look at the visible condensate line from the boiler. Note whether it is kinked, disconnected or leaking. Do not take the trap apart.
- Pressure gauge: write down the reading. Do not open the fill valve, bleed radiators or drain anything to adjust it.
- Record the pattern: note the time, which zones were calling, whether the hot water tank was heating, and any recent work on the system. A phone photo of the display each time helps.
When does Weil-McLain error code 24 become a licensed call, and what is the safety line?
Book a licensed technician if _24 shows up more than occasionally, if it arrives with cold zones, new noises, a changed pressure reading or water near the boiler, or if it started after any work on the heating system. Those are signs the cause is real and will keep returning until it is corrected. Purging air, replacing circulators or sensors, adjusting valves and correcting piping are technician jobs, and anything touching the gas train, burner, venting or control wiring requires a licensed gas fitter in BC.
Do not open the front cover or the burner compartment, do not jumper, unplug or swap sensors to make the code go away, and do not bypass any safety control. A boiler that is fooled into firing with reversed or stalled flow can overheat its heat exchanger.
Gas and carbon monoxide safety: if you smell gas (a rotten-egg odour), if a carbon monoxide alarm sounds, or if anyone in the home has headaches, dizziness or nausea that ease when they go outside, leave the home right away. Do not use light switches, phones or anything that could spark on the way out. Call FortisBC or 911 from outside. Every home with a gas boiler should have working carbon monoxide alarms near the sleeping areas and close to the mechanical room, and they should be tested regularly.
How our Weil-McLain error code 24 repair visit works
Diagnostic service calls are $189.00. That covers a licensed technician finding the actual cause with the right instruments, not guessing and swapping parts. Here is what the visit looks like from your side:
- Booking: tell us what you wrote down, including when the code appears and any recent work. We offer same-day where we can; it depends on the day’s calls, so we will give you an honest window rather than a promise.
- Safety first: the technician checks for gas leaks at the boiler connections and for carbon monoxide around the appliance before anything else.
- Reading the control: we review the lockout history and watch the live supply and return temperatures through a full heating call.
- Measuring: sensors are tested with a meter against the manufacturer’s published values, pipe temperatures are checked on both sides of the boiler, circulator direction is confirmed, and system pressure is verified.
- Tracing the flow: zone valves, circulators, flow checks, the air separator, strainers and the near-boiler piping are checked against how the system is supposed to move water.
- Explaining and quoting: you get a clear explanation of what we found and a written quote before any work beyond the diagnosis. Nothing is replaced without your approval.
- Repairing: the parts most often involved with this kind of fault are temperature sensors, circulators, zone valve actuators, flow-check valves and air vents, and sometimes a system flush with inhibitor treatment where sludge is the root cause.
- Testing the safeties: after the repair we run heat and hot water calls, confirm the return is cooler than the outlet, check the operating and high limits, confirm venting and combustion readings, and leave written notes of what was done.
Repair or replace a Weil-McLain boiler that keeps showing code 24?
Most _24 faults are repairs, not replacements. Air, a failed circulator, a bad sensor or a reversed pump are fixable on almost any boiler. Replacement becomes a fair question when the code is one symptom among several on an older boiler: a heat exchanger with heavy sludge damage or signs of overheating, repeated failures of the same parts, controls that are hard to source, or a system that was pieced together over decades and never piped properly. A heat exchanger or control board is among the more expensive parts on a gas boiler, so on an older unit we will tell you honestly whether that money is better put toward new equipment.
If replacement makes sense, the in-home estimate for a new boiler or installation is free, and if you go ahead with a replacement or new installation through BC Wide, the $189.00 diagnostic charge is waived and taken off the installation. A correct replacement is sized from a heat-loss assessment of your home, not matched to the old nameplate, and the near-boiler piping is laid out to the manufacturer’s installation instructions so flow problems like this one are designed out.
What you should see in writing on any boiler replacement quote: the equipment and why it was chosen, the piping and pump arrangement, venting route and terminal location, the gas permit and Technical Safety BC inspection, a system flush and water treatment plan, removal of the old boiler, and a commitment to record startup and combustion readings. If a quote leaves those out, ask before you sign.
Weil-McLain boiler error code 24 service across Greater Vancouver
We service hydronic boilers across Vancouver, Burnaby, Surrey, Richmond, Coquitlam and the rest of the Tri-Cities, the North Shore, New Westminster, Delta and Langley. Housing stock varies a lot across the region, and it shapes what we tend to find. Older houses in Vancouver, Burnaby and New Westminster can have hydronic systems that started with cast-iron radiators and were later extended or converted, which is where cross-connected piping and mismatched pumps often turn up. Some North Shore homes, built on slopes with several levels, run multiple zones and in-floor heat, so air trapped at high points and zones fighting each other are frequent suspects. In parts of Surrey, Langley, Delta and Richmond, newer houses and townhouses often use in-floor radiant heat with mixing controls, where a pump or flow-check problem can show up as a return reading higher than the boiler outlet. These are general patterns, not rules; your home is diagnosed on its own merits.
Metro Vancouver’s soft water matters here. Hydronic problems in this region are driven by sludge and corrosion debris, not hard-water scale, and that sludge is what slowly chokes flow through a heat exchanger and can contribute to flow-related lockouts. Our mild, wet climate also means long shoulder seasons with light, frequent heating calls, which is when marginal flow and air problems tend to show themselves. Wet leaves and debris around low vent terminals are a more common nuisance than snow, though a coastal cold snap can bring both.
In strata buildings and townhouses, boiler rooms can be shared or locked, so let us know if access needs to be arranged through a property manager, and remember that any change to venting or exterior terminals may need strata approval.
- BC Wide is an independent TSBC-licensed contractor serving Metro Vancouver since 1999: gas contractor licence LGA0090068, Class B gas licence CGA0028029.
- Work is done by our own licensed gas fitters, with permits and Technical Safety BC inspections pulled wherever the work requires them.
- You get a written quote before any work beyond the diagnosis.
- Boiler brands we service include Weil-McLain, IBC, Viessmann, Lochinvar, Buderus, Triangle Tube, Navien and Bosch. We are not a factory-authorized dealer or warranty centre for any brand; if your boiler is under warranty, we document our findings so you can take them to the manufacturer.
- Call (604) 473-9690 to book a visit anywhere in our Greater Vancouver service area.
More questions homeowners ask
What does Weil-McLain boiler error code 24 mean?
It means the boiler control has gone into a soft lockout because it measured return water hotter than outlet water. That usually points to a sensor problem or a water-flow problem such as reversed circulation or air in the boiler. It clears on its own once the readings return to normal; confirm the meaning against the manual for your unit.
Can I reset Weil-McLain error code 24 myself?
Usually there is nothing to reset, because _24 is a self-clearing soft lockout. If your owner manual allows a manual reset, try it once only, and do not keep cycling the power. If the code returns, the cause is real and needs a licensed technician to find it.
Is it safe to run my Weil-McLain boiler with code 24 showing?
The code is a protective lockout, not a gas or carbon monoxide warning, so the boiler is protecting itself rather than putting you at immediate risk. Running for long periods with poor or reversed flow is hard on the heat exchanger, so book a diagnosis if it keeps returning. If you ever smell gas or a CO alarm sounds, leave the home and call FortisBC or 911 from outside.
Why did my Weil-McLain boiler start showing code 24 after it was refilled or repaired?
The most common reason is air left in the system after it was drained and refilled, which stalls flow through the boiler. The other frequent cause after work is a circulator installed facing the wrong way or piping that was reconnected incorrectly. Both are corrected by a licensed technician purging the system and checking flow direction.
Who fixes Weil-McLain boiler error code 24 near me in Greater Vancouver?
BC Wide’s own licensed gas fitters diagnose and repair Weil-McLain boilers across Vancouver, Burnaby, Surrey, Richmond, the Tri-Cities, the North Shore, New Westminster, Delta and Langley. We are an independent TSBC-licensed contractor, not a dealer, and you get a written quote before any work beyond the diagnosis. Call (604) 473-9690 to book.
Does Weil-McLain code 24 mean my boiler needs to be replaced?
Usually not. Most cases come down to air, a circulator, a sensor or a piping issue, which are repairs. Replacement only comes up when the code is one of several problems on an older boiler, and if it does, the in-home estimate for a new boiler is free.
- Vaillant Boiler Code F.85 — Flow/return sensor fitted on the same pipe | BC Wide
- Vaillant Boiler Error Codes & Repair | Greater Vancouver | BC Wide
- Viessmann Boiler Code 02 — Safety chain / burner lockout | BC Wide
- Viessmann Boiler Code 0A — Fan speed fault | BC Wide
- Viessmann Boiler Code 0B — Wind conditions / low water flow | BC Wide
- Viessmann Boiler Code 0C — Power supply / flame-after-shutdown fault | BC Wide
- Viessmann Boiler Code 0D — Reset button pressed too often | BC Wide
- Viessmann Boiler Code 0F — Service / maintenance due | BC Wide
- Viessmann Boiler Code 10 — Outdoor temperature sensor short circuit | BC Wide
- Viessmann Boiler Code 18 — Outdoor temperature sensor open circuit | BC Wide
Frequently asked questions
How often should a boiler be serviced?
How much does a new boiler cost in Vancouver?
How long does a boiler last?
My boiler is making a banging or kettling noise. Is that dangerous?
Do you service Viessmann, IBC, Baxi, Laars, and Weil-McLain boilers?
Should I repair or replace my old boiler?
What HVAC services does BC Wide offer in Metro Vancouver?
How long has BC Wide been in business?
What areas do you serve?
What Greater Vancouver homeowners say about BC Wide
Get a Free Quote — Right From This Page
Request a Free Quote
Get Comfortable — Talk to BC Wide Today
Free, no-obligation quotes. TSBC-licensed local technicians serving Greater Vancouver since 1999.